Base Quantities Within The Protection; Internal Earth-Fault Protection Structure; Four Residual Overcurrent Steps - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 8
Current protection
8.2.7.4
8.2.7.5
8.2.7.6
196

Base quantities within the protection

The base quantities are entered as global settings for all functions in the IED. Base
current (IBase) shall be entered as rated phase current of the protected object in
primary amperes. Base voltage (UBase) shall be entered as rated phase-to-phase
voltage of the protected object in primary kV.

Internal earth-fault protection structure

The protection is internally divided into the following parts:
1.

Four residual overcurrent steps.

2.
Directional supervision element for residual overcurrent steps with integrated
directional comparison step for communication based earth-fault protection
schemes (permissive or blocking).
3.
Second harmonic blocking element with additional feature for sealed-in blocking
during switching of parallel transformers.
Each part is described separately in the following sections.
Four residual overcurrent steps
Each overcurrent step uses operating quantity Iop (residual current) as measuring
quantity. Each of the four residual overcurrent steps has the following built-in
facilities:
Directional mode can be set to Off/Non-directional/Forward/Reverse. By this
parameter setting the directional mode of the step is selected. It shall be noted that
the directional decision (Forward/Reverse) is not made within each residual
overcurrent step itself. The direction of the fault is determined in a directional
element common for all steps.
Residual current start value.
Type of operating characteristic. By this parameter setting it is possible to select
inverse or definitive time delay for step 1 and 4 separately. Step 2 and 3 are always
definite time delayed. All of the standard IEC and ANSI inverse characteristics
are available. For the complete list of available inverse curves please refer to
section
"Inverse time
Time delay related settings. By these parameter settings the properties like
definite time delay, minimum operating time for inverse curves and reset time
delay are defined.
Supervision by second harmonic blocking feature (On/Off). By this parameter
setting it is possible to prevent operation of the step if the second harmonic
content in the residual current exceeds the preset level.
Simplified logic diagram for one residual overcurrent step is shown in figure 93.
characteristics".
1MRK 502 048-UEN A
Technical manual