1MRK 502 048-UEN A
17.9.3
17.9.4
Technical manual

Function block

SMAI_20_1
BLOCK
SPFCOUT
DFTSPFC
AI3P
REVROT
AI1
^GRP1L1
AI2
^GRP1L2
AI3
^GRP1L3
AI4
^GRP1N
AIN
IEC09000137-1-en.vsd
IEC09000137 V1 EN
Figure 306:
SMAI_20_1 function block
SMAI_20_2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
IEC09000138-2-en.vsd
IEC09000138 V2 EN
Figure 307:
SMAI_20_2 to SMAI_20_12 function block
Note that input and output signals on SMAI_20_2 to SMAI_20_12 are
the same except for input signals GRPxL1 to GRPxN where x is equal
to instance number (2 to 12).

Signals

Table 509:
SMAI_20_1 Input signals
Name
Type
BLOCK
BOOLEAN
DFTSPFC
REAL
REVROT
BOOLEAN
GRP1L1
STRING
GRP1L2
STRING
GRP1L3
STRING
GRP1N
STRING
AI3P
AI1
AI2
AI3
AI4
AIN
Default
Description
0
Block group 1
20.0
Number of samples per fundamental cycle used for
DFT calculation
0
Reverse rotation group 1
-
First analog input used for phase L1 or L1-L2
quantity
-
Second analog input used for phase L2 or L2-L3
quantity
-
Third analog input used for phase L3 or L3-L1
quantity
-
Fourth analog input used for residual or neutral
quantity
Section 17
Basic IED functions
639