Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
8.10.5
Table 149:
VRPVOC Group settings (basic)
Name
Values (Range)
Operation
StartCurr
Characterist
tDef_OC
k
tMin
Operation_UV
StartVolt
tDef_UV
EnBlkLowV
BlkLowVolt
Table 150:
VRPVOC Group settings (advanced)
Name
Values (Range)
VDepFact
VDepMode
UHighLimit
Table 151:
VRPVOC Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
Technical manual

Settings

Unit
Off
-
On
2.0 - 5000.0
%IB
ANSI Ext. inv.
-
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
0.00 - 6000.00
s
0.05 - 999.00
-
0.00 - 6000.00
s
Off
-
On
2.0 - 100.0
%UB
0.00 - 6000.00
s
Off
-
On
0.0 - 5.0
%UB
Unit
5.0 - 100.0
-
Step
-
Slope
30.0 - 100.0
%UB
Unit
1 - 6
-
Step
Default
-
Off
1.0
120.0
-
IEC Norm. inv.
0.01
0.50
0.01
1.00
0.01
0.05
-
Off
0.1
50.0
0.01
1.00
-
Off
0.1
3.0
Step
Default
0.1
25.0
-
Slope
0.1
100.0
Step
Default
1
1
Section 8
Current protection
Description
Operation Off / On
Start current level in % of IBase
Time delay curve type for 51V
Independent (definite) time delay for OC
Time multiplier for the IDMT curves
Minimum operate time for IDMT curves
Operation of under-voltage stage (ANSI
27) Off / On
Operate undervoltage level for UV in % of
Ubase
Operate time delay in sec for definite time
use of UV
Enable internal low voltage level blocking
for UV
Internal low voltage blocking level for UV
in % of Ubase
Description
Start current level in % of pickup when U<
25% of UBase
Voltage dependent mode OC (step,
slope)
Voltage high limit setting in % of Ubase
Description
Selection of one of the Global Base Value
groups
251