1MRK 502 048-UEN A
13.9.5
Table 343:
TEIGGIO Group settings (basic)
Name
Values (Range)
Operation
tWarning
tAlarm
13.9.6
Technical manual
Settings
Unit
0 - 1
-
1.00 - 999999.99
s
1.00 - 999999.99
s
Operation principle
The elapsed time integrator (TEIGGIO) provides
•
time integration, accumulating the elapsed time when a given binary signal has
been high.
•
blocking and reset.
•
supervision of limit transgression and overflow.
•
retaining of the integrated value if any warning, alarm or overflow occurs.
Figure
234
describes the simplified logic of the function where the block "Time
Integration" covers the logics for the first two items listed above while the block
"Transgression Supervision Plus Retain" contains the logics for the last two.
tOverflow
tWarning
tAlarm
BLOCK
RESET
IN
IEC12000195 V2 EN
Figure 234:
TEIGGIO Simplified logic
TEIGGIO main functionalities are
•
integrate the elapsed time when IN has been high
Step
Default
1
1
0.01
600.00
0.01
1200.00
Loop Delay
Time Integration
Loop Delay
Section 13
Description
Operation Off / On
Time limit for warning supervision
Time limit for alarm supervision
Transgression Supervision
Plus Retain
IEC12000195-2-en.vsd
Logic
OVERFLOW
WARNING
ALARM
ACCTIME
467