Signals; Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
14.18.3
14.18.4
Table 434:
I103MEAS Non group settings (basic)
Name
Values (Range)
FunctionType
MaxIL1
MaxIL2
MaxIL3
MaxIN
MaxUL1
MaxUL2
MaxUL3
MaxUL1-UL2
MaxUN
MaxP
MaxQ
MaxF
Technical manual

Signals

Table 433:
I103MEAS Input signals
Name
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F

Settings

Unit
1 - 255
-
1 - 99999
A
1 - 99999
A
1 - 99999
A
1 - 99999
A
0.05 - 2000.00
kV
0.05 - 2000.00
kV
0.05 - 2000.00
kV
0.05 - 2000.00
kV
0.05 - 2000.00
kV
0.00 - 2000.00
MW
0.00 - 2000.00
MVA
45.0 - 66.0
Hz
Type
Default
Description
BOOLEAN
0
Block of service value reporting
REAL
0.0
Service value for current phase L1
REAL
0.0
Service value for current phase L2
REAL
0.0
Service value for current phase L3
REAL
0.0
Service value for residual current IN
REAL
0.0
Service value for voltage phase L1
REAL
0.0
Service value for voltage phase L2
REAL
0.0
Service value for voltage phase L3
REAL
0.0
Service value for voltage phase-phase L1-L2
REAL
0.0
Service value for residual voltage UN
REAL
0.0
Service value for active power
REAL
0.0
Service value for reactive power
REAL
0.0
Service value for system frequency
Step
Default
1
1
1
3000
1
3000
1
3000
1
3000
0.05
230.00
0.05
230.00
0.05
230.00
0.05
400.00
0.05
230.00
0.05
1200.00
0.05
1200.00
1.0
51.0
Section 14
Monitoring
Description
Function type (1-255)
Maximum current phase L1
Maximum current phase L2
Maximum current phase L3
Maximum residual current IN
Maximum voltage for phase L1
Maximum voltage for phase L2
Maximum voltage for phase L3
Maximum voltage for phase-phase L1-L2
Maximum residual voltage UN
Maximum value for active power
Maximum value for reactive power
Maximum system frequency
575