Section 20 Ied And Functionality Tests; Electromagnetic Compatibility Tests - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
Section 20
20.1
Technical manual
IED and functionality tests

Electromagnetic compatibility tests

Table 569:
Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference
tests
Conducted, common
mode
Radiated, amplitude-
modulated
Fast transient disturbance tests
Communication ports
Other ports
Surge immunity test
Communication
Other ports
Power supply
Power frequency (50 Hz)
magnetic field
3 s
Table continues on next page
IED and functionality tests
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz
and f=1.4...2.7 GHz
4 kV
4 kV
1 kV line-to-earth
2 kV line-to-earth, 1 kV line-to-
line
4 kV line-to-earth, 2 kV line-to-
line
1000 A/m
Section 20
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8, level 5