Settings; Monitored Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
8.5.5
Table 110:
CCRBRF Group settings (basic)
Name
Values (Range)
Operation
FunctionMode
BuTripMode
RetripMode
IP>
IN>
t1
t2
Table 111:
CCRBRF Group settings (advanced)
Name
Values (Range)
I>BlkCont
Table 112:
CCRBRF Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
8.5.6
Technical manual

Settings

Unit
Off
-
On
Current
-
Contact
Current&Contact
2 out of 4
-
1 out of 3
1 out of 4
Retrip Off
-
CB Pos Check
No CBPos Check
5 - 200
%IB
2 - 200
%IB
0.000 - 60.000
s
0.000 - 60.000
s
Unit
5 - 200
%IB
Unit
1 - 6
-

Monitored data

Table 113:
CCRBRF Monitored data
Name
IL1
IL2
IL3
IN
Step
Default
-
Off
-
Current
-
1 out of 3
-
Retrip Off
1
10
1
10
0.001
0.000
0.001
0.150
Step
Default
1
20
Step
Default
1
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
REAL
-
Section 8
Current protection
Description
Operation Off / On
Detection principle for back-up trip
Back-up trip mode
Operation mode of re-trip logic
Operate phase current level in % of IBase
Operate residual current level in % of
IBase
Time delay of re-trip
Time delay of back-up trip
Description
Current for blocking of CB contact
operation in % of IBase
Description
Selection of one of the Global Base Value
groups
Unit
Description
A
Measured current in
phase L1
A
Measured current in
phase L2
A
Measured current in
phase L3
A
Measured residual
current
223