Directional Residual Current Protection Measuring 3I ·Cos - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
8.3.7.2
Technical manual
Directional residual current protection measuring 3I
φ is defined as the angle between the residual current 3I
jRCADir
Uref = -3U
e
, that is -3U
0
(φ=ang(3I
)-ang(U
) ). RCADir is normally set equal to 0 in a high impedance
0
ref
earthed network with a neutral point resistor as the active current component is
appearing out on the faulted feeder only. RCADir is set equal to -90° in an isolated
network as all currents are mainly capacitive. The function operates when 3I
gets larger than the set value.
IEC06000648 V3 EN
Figure 100:
RCADir set to 0°
U
ref
3 ⋅
I
cos
ϕ
0
IEC06000649 V3 EN
Figure 101:
RCADir set to -90°
rotated by the set characteristic angle RCADir
0
RCADir
=
0 ,
ROADir
3I
0
ϕ =
ang(3I ) ang(3U
)
0
ref
3U
3I cos
ϕ
0
IEC06000648-3-en.vsd
RCADir
= −
90 ,
ROADir
=
90
3I
0
ϕ =
ang I
(3 )
ang U
(
)
0
ref
3U
0
IEC06000649_3_en.vsd
Section 8
Current protection
·cos φ
0
and the reference voltage.
0
=
0
=
U
0
ref
·cos φ
0
207