Identification; Functionality; Settings; Authority Check Athchck - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 17
Basic IED functions
17.11.1
17.11.2
17.11.3
Table 521:
GBASVAL Non group settings (basic)
Name
UBase
IBase
SBase
17.12
17.12.1
17.12.2
648

Identification

Function description
Global base values

Functionality

Global base values function (GBASVAL) is used to provide global values, common
for all applicable functions within the IED. One set of global values consists of values
for current, voltage and apparent power and it is possible to have six different sets.
This is an advantage since all applicable functions in the IED use a single source of
base values. This facilitates consistency throughout the IED and also facilitates a
single point for updating values when necessary.
Each applicable function in the IED has a parameter, GlobalBaseSel, defining one out
of the six sets of GBASVAL functions.

Settings

Values (Range)
Unit
0.05 - 1000.00
kV
1 - 50000
A
0.050 - 5000.000
MVA

Authority check ATHCHCK

Identification

Function description
Authority check

Functionality

To safeguard the interests of our customers, both the IED and the tools that are
accessing the IED are protected, by means of authorization handling. The
authorization handling of the IED and the PCM600 is implemented at both access
points to the IED:
IEC 61850
identification
GBASVAL
Step
Default
0.05
132.00
1
1000
0.001
229.000
IEC 61850
identification
ATHCHCK
1MRK 502 048-UEN A
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Description
Global base voltage
Global base current
Global base apparent power
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Technical manual