Settings; Monitored Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
9.2.5
Table 162:
OV2PTOV Group settings (basic)
Name
Values (Range)
Operation
OperationStep1
Characterist1
OpMode1
U1>
t1
t1Min
k1
OperationStep2
OpMode2
U2>
t2
Table 163:
OV2PTOV Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
ConnType
9.2.6
Technical manual

Settings

Unit
Off
-
On
Off
-
On
Definite time
-
Inverse curve A
Inverse curve B
Inverse curve C
1 out of 3
-
2 out of 3
3 out of 3
1 - 200
%UB
0.00 - 6000.00
s
0.000 - 60.000
s
0.05 - 1.10
-
Off
-
On
1 out of 3
-
2 out of 3
3 out of 3
1 - 200
%UB
0.000 - 60.000
s
Unit
1 - 6
-
PhN DFT
-
PhN RMS
PhPh DFT
PhPh RMS

Monitored data

Table 164:
OV2PTOV Monitored data
Name
UL1
UL2
UL3
Step
Default
-
Off
-
On
-
Definite time
-
1 out of 3
1
120
0.01
5.00
0.001
5.000
0.01
0.05
-
On
-
1 out of 3
1
150
0.001
5.000
Step
Default
1
1
-
PhN DFT
Type
Values (Range)
REAL
-
REAL
-
REAL
-
Section 9
Voltage protection
Description
Operation Off / On
Enable execution of step 1
Selection of time delay curve type for step
1
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 1
Voltage start value (DT & IDMT) in % of
UBase for step 1
Definite time delay of step 1
Minimum operate time for inverse curves
for step 1
Time multiplier for the inverse time delay
for step 1
Enable execution of step 2
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 2
Voltage start value (DT & IDMT) in % of
UBase for step 2
Definite time delay of step 2
Description
Selection of one of the Global Base Value
groups
Group selector for connection type
Unit
Description
kV
Voltage in phase L1
kV
Voltage in phase L2
kV
Voltage in phase L3
265