Elapsed Time Integrator With Limit Transgression And Overflow Supervision Teigapc - ABB RELION RET670 Applications Manual

Relion 670 series transformer protection version 2.2 ansi
Hide thumbs Also See for RELION RET670:
Table of Contents

Advertisement

1MRK 504 163-UUS A
17.12
17.12.1
17.12.2
17.12.3
Transformer protection RET670 2.2 ANSI
Application manual
Name of OUTx
Type
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted by the
ITBGAPC function block.
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
Identification
Function Description
Elapsed time integrator
Application
The function TEIGAPC is used for user-defined logics and it can also be used for
different purposes internally in the IED. An application example is the integration of
elapsed time during the measurement of neutral point voltage or neutral current at
earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow
indication is fixed to 999999.9 seconds.
Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
Description
Value when
activated
Output 14
8192
Output 15
16384
Output 16
32768
IEC 61850
IEC 60617
identification
identification
TEIGAPC
-
Section 17
Value when
deactivated
0
0
0
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
ANSI/IEEE C37.2 device
number
-
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
Logic
857