1MRK 502 048-UEN A
8.7.5
8.8
8.8.1
8.8.2
Technical manual
(
)
= ×
+
-
×
S
k S
1 k S
Old
Calculated
EQUATION1959 V1 EN
Where
S
is a new measured value to be used for the protection function
S
is the measured value given from the function in previous execution cycle
old
S
is the new calculated value in the present execution cycle
Calculated
k
is settable parameter by the end user which influence the filter properties
TD
Default value for parameter k is 0.00. With this value the new calculated value is
immediately given out without any filtering (that is without any additional delay).
When k is set to value bigger than 0, the filtering is enabled. A typical value for k=0.92
in case of slow operating functions.
Technical data
Table 134:
GOPPDOP, GUPPDUP technical data
Function
Power level
Characteristic angle
Timers
Accidental energizing protection for synchronous
generator AEGGAPC
Identification
Function description
Accidental energizing protection for
synchronous generator
Functionality
Inadvertent or accidental energizing of off-line generators has occurred often enough
due to operating errors, breaker head flashovers, control circuit malfunctions, or a
combination of these causes. Inadvertently energized generator operates as induction
Range or value
SBase
(0.0–500.0)% of
SBase
(1.0-2.0)% of
SBase
(2.0-10)% of
(-180.0–180.0) degrees
(0.010 - 6000.000) s
IEC 61850
IEC 60617
identification
identification
AEGGAPC
Section 8
Current protection
(Equation 73)
Accuracy
± 1.0% of S
at S < S
r
r
± 1.0% of S at S > S
r
< ± 50% of set value
< ± 20% of set value
2 degrees
± 0.5% ± 25 ms
ANSI/IEEE C37.2
device number
U<I>
50AE
239