Section 13
Logic
13.5.5
13.5.6
13.5.7
456

Settings

The function does not have any parameters available in local HMI or Protection and
Control IED Manager (PCM600)

Monitored data

Table 332:
B16I Monitored data
Name
Type
OUT
INTEGER

Operation principle

The Boolean 16 to integer conversion function (B16I) will transfer a combination of
up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value
according to the table below from 0 to 32768. This follows the general formula: INx
x-1
= 2
where 1≤x≤16. The sum of all the values on the activated INx will be available
on the output OUT as a sum of the integer values of all the inputs INx that are activated.
OUT is an integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it
corresponds to that integer 65535 is available on the output OUT. The B16I function
is designed for receiving up to 16 booleans input locally. If the BLOCK input is
activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block B16I
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
Table continues on next page
Values (Range)
Unit
-
-
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
0
Input 11
0
Input 12
0
Input 13
1MRK 502 048-UEN A
Description
Output value
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
1024
0
2048
0
4096
0
Technical manual