ABB REG650 Technical Manual page 331

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 048-UEN A
Name
Values (Range)
FreqDiffMin
FreqDiffMax
FreqRateChange
tBreaker
tClosePulse
tMaxSynch
tMinSynch
OperationSC
UDiffSC
FreqDiffA
FreqDiffM
PhaseDiffA
PhaseDiffM
tSCA
tSCM
AutoEnerg
ManEnerg
ManEnergDBDL
tAutoEnerg
tManEnerg
Technical manual
Unit
0.003 - 0.250
Hz
0.050 - 0.500
Hz
0.000 - 0.500
Hz/s
0.000 - 60.000
s
0.050 - 60.000
s
0.00 - 6000.00
s
0.000 - 60.000
s
Off
-
On
0.02 - 0.50
pu
0.003 - 1.000
Hz
0.003 - 1.000
Hz
5.0 - 90.0
Deg
5.0 - 90.0
Deg
0.000 - 60.000
s
0.000 - 60.000
s
Off
-
DLLB
DBLL
Both
Off
-
DLLB
DBLL
Both
Off
-
On
0.000 - 60.000
s
0.000 - 60.000
s
Step
Default
0.001
0.010
0.001
0.200
0.001
0.300
0.001
0.080
0.001
0.200
0.01
600.00
0.001
2.000
-
On
0.01
0.15
0.001
0.010
0.001
0.010
1.0
25.0
1.0
25.0
0.001
0.100
0.001
0.100
-
DLLB
-
Both
-
Off
0.001
0.100
0.001
0.100
Section 12
Description
Minimum frequency difference limit for
synchronizing
Maximum frequency difference limit for
synchronizing
Maximum allowed frequency rate of
change
Closing time of the breaker
Breaker closing pulse duration
Resets synch if no close has been made
before set time
Minimum time to accept synchronizing
conditions
Operation for synchronism check function
Off/On
Voltage difference limit for synchrocheck
in p.u of set voltage base value
Frequency difference limit between bus
and line Auto
Frequency difference limit between bus
and line Manual
Phase angle difference limit between bus
and line Auto
Phase angle difference limit between bus
and line Manual
Time delay output for synchrocheck Auto
Time delay output for synchrocheck
Manual
Automatic energizing check mode
Manual energizing check mode
Manual dead bus, dead line energizing
Time delay for automatic energizing
check
Time delay for manual energizing check
Control
325

Advertisement

Table of Contents
loading