Fixed Frequency Selection; Fixed Frequency - Siemens SINAMICS V10 Operating Instructions Manual

Table of Contents

Advertisement

Par. No.
Name
P1020

Fixed frequency selection 1

Common settings:
P1020 = 722.0 => Digital input 1
Dependency:
Accessible only if P0701 - P0703 = 99 (enabling the use of 722.0 - 722.2)
See the table in P1001 (fixed frequency 1) for the description of how to use fixed frequencies.
If both 1020 and 1021 are selected, the fixed setpoint is the sum of P1001 and 1002.
P1021
Fixed frequency selection 2
Common settings:
P1021 = 722.1 ==> Digital input 2
Dependency:
Accessible only if P0701 - P0703 = 99 (enabling the use of 722.0 - 722.2)
See the table in P1002 (fixed frequency 2) for the description of how to use fixed frequencies
If both 1020 and 1021 are selected, the fixed setpoint is the sum of P1001 and 1002.
Note: For users who are familiar with MM4 serial converters, parameters P1020 and P1021 have the same function with
MM4 converters if P1016 and P1017 are set to 1.
P1001

Fixed frequency 1

Defines fixed frequency setpoint 1.
There are three options available for the selection of fixed frequencies:
1. Direct selection (P0701 ... P0703 = 15)
In this mode of operation, 1 digital input selects 1 fixed frequency.
If several inputs are active at the same time, the selected frequencies are summed up.
2. Direct selection + ON command (P0701 ... P0703 = 16)
The fixed frequency selection integrates fixed frequencies with an ON command.
In this mode of operation, 1 digital input selects 1 fixed frequency.
If several inputs are active at the same time, the selected frequencies are summed up.
3. Direct selection multifunction (P0701 ... P0703 = 99; P1020 = 722.0 ... 2 and P1021 = 722.0 ... 2)
In this mode of operation, 1 digital input selects 1 fixed frequency.
If several inputs are active at the same time, the selected frequencies are summed up.
This mode is an alternative of option 1, except P0701 ... P0703 = 99, the used digital input can also act
as other functions.
P1002
Fixed frequency 2
Defines fixed frequency setpoint 2.
For Details, see parameter P1001 (fixed frequency 1).
P1003
Fixed frequency 3
Defines fixed frequency setpoint 3
For Details, see parameter P1001(fixed frequency 1)
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
Range
Default
0.0 - 2036.F
0.0
0.0 - 2036.F
0.0
-300.00 - 300.00
-300.00 - 300.00
-300.00 - 300.00
Parameter list
Unit
-
-
0.00
Hz
5.00
Hz
10.00
Hz
93