Connecting Power Supply To The Motor; Power And Motor Connections; Types Of Siemens Line Fuses (Recommended) - Siemens SINAMICS V10 Operating Instructions Manual

Table of Contents

Advertisement

5.2.2

Connecting power supply to the motor

Power and motor connections

Figure 5-15
Ensure that the appropriate fuses with specified current ratings are connected between the
power supply and the inverter (See table below for the type of recommended SIEMENS fuses
for different frame sizes. ). For detailed fuse specification, consult your local inverter
distributor or visit the SIEMENS website concerned.
Table 5-9
Inverter variant
Frame Size A
Frame Size B
Frame Size C
Frame Size D
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
3-phase AC 400V
L1
L2
L3
Contactor
Fuse
Power and motor connections
CAUTION

Types of SIEMENS line fuses (recommended)

Inverter output power rating (kW)
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
SINAMICS V10
L3
L2
L1
PE
PE
5.2 Electrical installation
W
W
V
V
U
U
Fuse type
Fuse current rating (A)
3NA3803
10
3NA3803
10
3NA3803
10
3NA3803
10
3NA3805
16
3NA3805
16
3NA3807
20
3NA3807
20
3NA3810
25
3NA3814
35
3NA3817
40
3NA3820
50
3NA3822
63
Installation
Motor
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents