Installation
5.2 Electrical installation
Layout of interfaces other than PE terminals
Frame Size D
Mains input connection
Digital outputs
(1, 2)
Digital inputs
(5, 6, 7, 8, 9)
Figure 5-13
Layout of interfaces other than PE terminals (example)
Table 5-6
Inverter variant
Frame Size A
Frame Size B
Frame Size C
Frame Size D
NOTICE
Depending on your particular application, you can set both DIP-switches to required positions.
Digital inputs and analog inputs/outputs provide the SELV voltages.
34
For Frame Size D, it's necessary to
lever up the housing cover before
wiring.
DIP-switches
Motor output connection
(U, V, W)
(L1, L2, L3)
Analog inputs/outputs
(13, 14, 15, 16, 17, 18)
Tightening torques for motor output (U, V, W) and mains input terminals (L1, L2, L3)
Cover lock
DIGITAL
DIGITAL
OUTPUT
INPUT
Max. tightening torque for motor output and mains
input terminals (Nm)
0.6
0.6
1.2
2.5
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
Cover lock
ANALOG INPUT
IU
AND OUTPUT
SWITCH
Factory default positions
SINAMICS V10