Cloning parameters with the operator panel

A single parameter set can be uploaded into an inverter, and then downloaded into another
inverter. To clone a parameter set from one inverter to another one, please follow below
procedures:
1. Connect the operator panel to the inverter;
2. Ensure that it is safe to stop the inverter;
3. Stop the inverter;
4. Enter into "Operation mode ⑤ - Access all the parameters (Page 71)" mode, and set P0800
5. The operator panel displays "busy" during the parameter uploading;
6. During the parameter uploading, both the operator panel and the inverter will not give any
7. When the parameter uploading has been completed successfully, the operator panel
8. If the parameter uploading has failed, F0055 will be displayed on the operator panel. In this
9. Remove the operator panel from the inverter;
10.Connect the operator panel to a new inverter;
11.Ensure that power has been applied to the inverter;
12.Enter into " Operation mode ⑤ - Access all the parameters (Page 71)" mode, and set P0801
13.The operator panel displays "busy" or "- - "during the parameter downloading;
14.During the parameter downloading, both the operator panel and the inverter will not give
15.When the parameter downloading has been completed successfully, the operator panel
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
Disabled
All parameters and connection macros reset
All parameters (except motor data P0304, P0305, P0307 ... P0311, P0320, P0335,
P0350) and connection macro settings reset
= 1 to start uploading parameters;
response to any commands;
display returns to its normal state while the inverter returns to a ready state;
case, please check the operator panel to clear this fault, and try uploading parameters again;
= 1 to start downloading parameters;
any response to any command;
returns to its normal state while the inverter returns to a ready state;
6.8 Cloning parameters with the operator panel