Fault List - Siemens SINAMICS V10 Operating Instructions Manual

Table of Contents

Advertisement

Acknowledging alarm(s)
In the event of an alarm, no key or button is required for acknowledging or clearing the alarm
code. After the alarm cause is removed, the alarm code will automatically disappear.
Note
When multi-alarms occur, the alarm code is always displayed as x.Axxx. For example:
"1.A501" = The first alarm code A0501
"2.A503" = The second alarm code A0503
To view the alarm history, go to r2110.

Fault list

Fault
F0001
Overcurrent
F0002
Overvoltage
F0003
Undervoltage
F0004
Inverter overtemp.
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
Possible Causes
● Short-circuit at the output
● Ground fault
● Excessively large motor (the motor
power rating P0307 is greater than the
inverter power r0206)
● Defective final stage (end stage)
● DC link voltage (r0026) higher than the
overvoltage threshold (refer to
parameter r0026)
● Ground fault
● Line voltage failed
● Shock stressing outside the permissible
limits
● Inadequate cooling
● Ambient temperature is too high
Diagnose & Remedy
● Are the cable lengths within the limit values?
● Does the motor cable or motor have either a
short-circuit or ground fault?
● Do the motor parameters correspond to those of
the motor being used?
● Is the motor overloaded or stalled (locked rotor)?
● Increase the accelerating time.
● Reduce the gain (P2280)
● Use a motor with a lower power rating
● Is the stator resistance value (P0350) correct ?
● Is the line supply voltage within the permissible
range?
● Has the DC current DC link monitoring been
enabled (P1240) and correctly parameterized?
● Extend the deceleration ramp (ramp-down time
P1121, P1135)
● Remove the ground fault
● Is the required braking power within the
permissible limits?
● Is the line supply voltage within the permissible
range?
● is the line supply voltage stable with respect to
sporadic failures and voltage dips (brown-outs)?
● Is the pulse frequency P1800 set to the factory
setting? If required, reset P1800.
● Does the ambient temperature lie within the
permissible limits?
● Reduce the load and / or ensure adequate
cooling
● Does the fan rotate if the inverter is operational?
Troubleshooting
109