Typical connection mode 7 (C07)

Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
2. In REM mode, motor start/stop and rotation direction can be controlled via an external PLC
The DIP-switch settings
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
Select connection macro C06 with the operator panel after the wiring (please refer to
"Operation mode
will be automatically finished.)
Parameter name
Selected connection macro and application macro
Motor I
t reaction
2
Function of digital input 1
Function of digital input 2
Function of digital input 3
Selection of frequency setpoint
PNP/NPN digital inputs
operator panel.
(PNP type) connected to DI1 and DI2, motor speed via an external signal source.
3 AC 400 V
L1
L2
L3
PE
Fuse
Contactor
L3
PE L1
L2
SINAMICS V10 Inverter
U V
W
M
3~
Factory defaut setting:
Lit while inverter running or alarm
Inverter running: Lamp ON
Dim while inverter fault
Inverter in any other status: Lamp OFF
Figure 6-7
Typical connection mode 7 (C07)
- Connection macro selection", and then below parameter settings
PLC (PNP type outputs)
8
9
5
6
7
+24V
0V
DI1
DI2
DI3
Digital Input
I
I
U
AO
AO
AI
(V)
(mA)
(mA)
DIP-switches
Digital Output
DO1 DO1
1
2
N
L
220 AC Supply
6.1 Typical connection modes
Range
C0100 - C1105
0 - 2
0 - 99
0 - 99
0 - 99
0 - 53
0 - 1
Connection macro: C07
AO
D/A U
M
RPM Meter
N
16
18
14
15
17
13
AI1- AI1+ AO1+
AO1-
0V
+10V
Analog Input/Analog Output
U
AI
(V)
RS-485
Com A Com B
P6V5 M
Operator Panel
Commissioning
Unit
Default
- -
C06xx*
- -
2
- -
1
- -
15
- -
15
- -
3
- -
1
49