Commissioning
6.1 Typical connection modes
Table 6-10
Par. No.
r0007
P0610
P0701
P0702
P0703
P1000
P0725
* "xx" means current application macro.
NOTICE
The PI controller function is valid only in this connection mode and when the current control
mode is set to REM mode.
In this connection mode, PI setpoint must be set via P2240 and feedback value shall,
depending on actually connected sensor, be scaled via P0753 to P0761.
Besides parameters listed in Auto hotspot , P2280 (default value: 0.500), P2285 (default
value: 10.000s) and P2293 (default value: 10.00s) are also related to connection mode.
54
Select connection macro C10 with the operator panel after the wiring (please refer to
"Operation mode
- Connection macro selection", and then below parameter settings
will be automatically finished.)
Parameter name
Selected connection macro and application macro
Motor I
t reaction
2
Function of digital input 1
Function of digital input 2
Function of digital input 3
Selection of frequency setpoint
PNP/NPN digital inputs
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
Range
Unit
C0100 - C1105
- -
0 - 2
- -
0 - 99
- -
0 - 99
- -
0 - 99
- -
0 - 53
- -
0 - 1
- -
SINAMICS V10
Default
C10xx*
2
1
13
14
1
1