Typical Connection Mode 3 (C03) - Siemens SINAMICS V10 Operating Instructions Manual

Table of Contents

Advertisement

Table 6-2
Par. No.
r0007
P0610
P0701
P0702
P0703
P1000
P0725
* "xx" means current application macro.

Typical connection mode 3 (C03)

Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
2. In REM mode, motor start/stop can be controlled via an external signal source connected
The DIP-switch settings
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number)
Select connection macro C02 with the operator panel after the wiring (please refer to
"Operation mode
will be automatically finished.)
Parameter name
Selected connection macro and application macro
Motor I
t reaction
2
Function of digital input 1
Function of digital input 2
Function of digital input 3
Selection of frequency setpoint
PNP/NPN digital inputs
operator panel.
to DI1, motor speed via an external potentiometer.
3 AC 400 V
L1
L2
L3
PE
Fuse
Contactor
PE L1
L2
L3
SINAMICS V10 Inverter
U V
W
M
3~
Factory defaut setting:
Lit while inverter running or alarm
Inverter running: Lamp ON
Dim while inverter fault
Inverter in any other status: Lamp OFF
Figure 6-3
Typical connection mode 3 (C03)
- Connection macro selection", and then below parameter settings
6
7
8
9
5
+24V
0V
DI1
DI2
DI3
Digital Input
I
I
U
AO
AI
AO
(V)
(mA)
(mA)
Digital Output
DIP-switches
DO1 DO1
1
2
N
L
220 AC Supply
6.1 Typical connection modes
Range
C0100 - C1105
0 - 2
0 - 99
0 - 99
0 - 99
0 - 53
0 - 1
Connection macro: C03
Speed Reference
Potentiometer
RPM Meter
N
16
18
13
14
15
17
AI1- AI1+ AO1+
AO1-
0V
+10V
Analog Input/Analog Output
U
AI
(V)
RS-485
Com A Com B
P6V5 M
Operator Panel
Commissioning
Unit
Default
- -
C02xx*
- -
2
- -
13
- -
14
- -
1
- -
1
- -
1
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents