3 Commissioning
Motor data for parameterization
3.2.4
44
www.eltra-trade.com
P0308 P0310
50 Hz
Cos
0.81
j
65%
P0309
P0305 P0311 P0307
Figure 3-7
Typical Motor Rating Plate Example
NOTICE
Ø P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters is
shown depending on the settings of P0100.
Ø P0307 indicates kW or HP depending upon the setting of P0100. For detailed
information, please see the Parameter List.
Ø Changing motor parameters is not possible unless P0010=1.
Ø Ensure that the inverter is configured correctly to the motor.
Reset to Factory default
To reset all parameters to the factory default settings; the following parameters
should be set as follows (BOP-2 or Communication Option needed):
1. Set P0010=30.
2. Set P0970=1.
NOTE
The reset process can take up to 3 minutes to complete.
P0304
3_Mot
Nr. ED510 3053
IEC 56
IP54
Rot KL 16
IM B3
230/400V
60 Hz
440V Y
0.34A
0.61 0.35 A
0.14 kW
0.12kW
Cos
0.81
j
2800 / min
S.F. -- 1.15
MICROMASTER 430
12.022
I.CI.F
3310 /min
Operating Instructions
6SE6400-5AC00-0BP0
info@eltra-trade.com