Restoring parameter defaults

Restoring parameter defaults by this method saves the default values in
the drives memory. User security status (00.010) and User security code
(00.025) are not affected by this procedure).
Procedure
1. Ensure the drive is not enabled, i.e. terminal 11 is open or Pr 06.015
is OFF (0)
2. Select 'Def.50' or 'Def.60' in Pr mm.000. (alternatively, enter 1233
(50 Hz settings) or 1244 (60 Hz settings) in Pr mm.000).
3. Either:
Press the red
reset button
Carry out a drive reset through serial communications by setting
Pr 10.038 to 100
5.9

Parameter access level and security

The parameter access level determines whether the user has access to
Menu 0 only or to all the advanced menus (Menus 1 to 22) in addition to
Menu 0.
The User Security determines whether the access to the user is read
only or read write.
Both the User Security and Parameter Access Level can operate
independently of each other as shown in table Table 5-5.
Table 5-5 Parameter access level and security
User
security
Access level
status
(11.044)
Open
0
Menu 0
Closed
Open
1
All Menus
Closed
Open
Read-only
2
Menu 0
Closed
Open
3
Read-only
Closed
Open
4
Status only
Closed
Open
5
No access
Closed
The default settings of the drive are Parameter Access Level Menu 0
and user Security Open i.e. read / write access to Menu 0 with the
advanced menus not visible.
76
Electrical
Getting
Basic
installation
started
parameters
User
Menu 0
Advanced
security
status
menu status
RW
Not visible
RO
Not visible
RW
RW
RO
RO
RO
Not visible
RO
Not visible
RO
RO
RO
RO
Not visible
Not visible
Not visible
Not visible
Not visible
Not visible
Not visible
Not visible
Running the
NV Media
Optimization
motor
Card
5.9.1
User Security Level / Access Level
The drive provides a number of different levels of security that can be set
by the user via User Security Status (11.044); these are shown in the
table below.
User Security
Status
(Pr 11.044)
All writable parameters are available to be edited but
LEVEL.0 (0)
only parameters in Menu 0 are visible
All parameters are visible and all writable parameters
ALL (1)
are available to be edited
Access is limited to Menu 0 parameters only. All
r.only.0 (2)
parameters are read-only
All parameters are read-only however all menus and
r.only.A (3)
parameters are visible
The keypad remains in status mode and no
Status (4)
parameters can be viewed or edited
The keypad remains in status mode and no
parameters can be viewed or edited. Drive
no.acc (5)
parameters cannot be accessed via a comms/fieldbus
interface in the drive or any option module
5.9.2
Changing the User Security Level /Access
Level
The security level is determined by the setting of Pr 00.010 or Pr 11.044.
The Security Level can be changed through the keypad even if the User
Security Code has been set.
5.9.3
User Security Code
The User Security Code, when set, prevents write access to any of the
parameters in any menu.
Setting User Security Code
Enter a value between 1 and 9999 in Pr 00.025 and press the
button; the security code has now been set to this value. In order to
activate the security, the Security level must be set to desired level in
Pr 00.010. When the drive is reset, the security code will have been
activated and the drive returns to Menu 0. The value of Pr 00.025 will
return to 0 in order to hide the security code.
Unlocking User Security Code
Select a parameter that need to be edited and press the
the display will now show 'Co'. Use the arrow buttons to set the security
code and press the
entered, the display will revert to the parameter selected in edit mode.
If an incorrect security code is entered, the following message 'Co.Err' is
displayed, and the display will revert to parameter view mode.
Disabling User Security
Unlock the previously set security code as detailed above. Set Pr 00.025
to 0 and press the
disabled, and will not have to be unlocked each time the drive is
powered up to allow read / write access to the parameters.
5.10
Displaying parameters with non-
default values only
By selecting 'diff.d' in Pr mm.000 (Alternatively, enter 12000 in
Pr mm.000), the only parameters that will be visible to the user will be
those containing a non-default value. This function does not require a
drive reset to become active. In order to deactivate this function, return
to Pr mm.000 and select 'none' (alternatively enter a value of 0). Please
note that this function can be affected by the access level enabled, refer
to section 5.9 Parameter access level and security on page 76 for
further information regarding access level.
Advanced
Technical data
Diagnostics
parameters
Description
button. With the correct security code
button. The User Security has now been