Emerson unidrive m200 User Manual page 12

Hide thumbs Also See for unidrive m200:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
Table 2-3 400 V drive ratings (380 V to 480 V ±10 %)
Model
02400013
02400018
Frame size 2
02400023
02400032
02400041
03400056
Frame size 3
03400073
03400094
04400135
Frame size 4
04400170
05400270
Frame size 5
05400300
06400350
Frame size 6
06400420
06400470
Table 2-4 575 V drive ratings (500 V to 575 V ±10 %)
Model
05500030
Frame size 5
05500040
05500069
06500100
06500150
06500190
Frame size 6
06500230
06500290
06500350
2.2.1
Typical short term overload limits
The maximum percentage overload limit changes depending on the selected motor. Variations in motor rated current, motor power factor and motor
leakage inductance all result in changes in the maximum possible overload. The exact value for a specific motor can be calculated using the
equations detailed in Menu 4 in the Parameter Reference Guide.
Typical values are shown in the table below for RFC-A and open loop (OL) modes:
Table 2-5 Typical overload limits
Operating mode
Normal Duty overload with motor rated
current = drive rated current
Heavy Duty overload with motor rated
current = drive rated current
Generally the drive rated current is higher than the matching motor rated current allowing a higher level of overload than the default setting.
The time allowed in the overload region is proportionally reduced at very low output frequency on some drive ratings.
NOTE
The maximum overload level which can be attained is independent of the speed.
12
Electrical
Getting
Basic
installation
started
parameters
Normal Duty
Maximum
Nominal
Motor
continuous
power at
power at
output
400 V
460 V
current
A
kW
30
15
31
15
38
18.5
48
22
63
30
Normal Duty
Maximum
Nominal
Motor
continuous
power at
power at
output
575 V
575 V
current
A
kW
3.9
2.2
6.1
4
10
5.5
12
7.5
17
11
22
15
27
18.5
34
22
43
30
RFC From cold
110 % for 165 s
180 % for 3 s
Running the
NV Media
Optimization
motor
Card
Maximum
Peak
continuous
current
output
current
hp
A
A
1.3
1.8
2.3
3.2
4.1
5.6
7.3
9.4
13.5
17
20
33
27
20
34.1
30
25
41.8
35
30
52.8
42
40
69.3
47
Maximum
Peak
continuous
current
output
current
hp
A
A
3
4.3
3
5
6.7
4
7.5
11
6.9
10
13.2
10
15
18.7
15
20
24.2
19
25
29.7
23
30
37.4
29
40
47.3
35
RFC From 100 %
110 % for 9 s
180 % for 3 s
Advanced
Technical data
Diagnostics
parameters
Heavy Duty
Open
RFC
Nominal
loop
peak
power at
peak
current
400 V
current
A
A
kW
2
2.3
0.37
2.7
3.2
0.55
3.5
4.1
0.75
4.8
5.8
1.1
6.2
7.4
1.5
8.4
10.1
2.2
11
13.1
14.1
16.9
20.3
24.3
5.5
25.5
30.6
7.5
40.5
54
11
45
60
15
52.5
70
15
63
84
18.5
70.5
94
22
Heavy Duty
Open
RFC
Nominal
loop peak
peak
power at
current
current
575 V
A
A
kW
4.5
6
1.5
6
8
2.2
10.3
13.8
15
20
5.5
22.5
30
7.5
28.5
38
11
34.5
46
15
43.5
58
18.5
52.5
70
22
Open loop from cold
Open loop from 100 %
110 % for 165 s
110 % for 9 s
150 % for 60 s
150 % for 8 s
Unidrive M200 / M201 User Guide
UL Listing
Motor
power at
460 V
hp
0.5
0.75
1
1.5
2
3
3
3
4
5
7.5
10
20
20
25
30
30
Motor
power at
575 V
hp
2
3
4
5
7.5
10
15
20
25
30
Issue Number: 4