These trip numbers are reserved trip numbers for future use.
Trip Number
01
09
11 - 12
14 - 17
23, 29
38 - 39
94 - 96
99
103 - 108
103 - 108
110 - 111
110 - 111
168 - 174
168 - 174
176
190 - 198
205 - 214
190 – 198
216 - 217
205 - 214
223 - 224
234
216 - 217
238 - 244
223 - 224
249
252 - 254
238 - 244
252-254
rS
Measured resistance has exceeded the parameter range
The rS trip indicates that the measured stator resistance during an autotune test has exceeded the maximum possible
value of Stator Resistance (05.017).
The stationary autotune is initiated using the autotune function (Pr 05.012) or in open loop vector mode (Pr 05.014) on the
first run command after power up in mode 4 (Ur_I) or on every run command in modes 0 (Ur_S) or 3 (Ur_Auto). This trip
can occur if the motor is very small in comparison to the rating of the drive.
Recommended actions:
33
Check the motor cable / connections
Check the integrity of the motor stator winding using a insulation tester
Check the motor phase to phase resistance at the drive terminals
Check the motor phase to phase resistance at the motor terminals
Ensure the stator resistance of the motor falls within the range of the drive model
Select fixed boost mode (Pr 05.014 = Fd) and verify the output current waveforms with an oscilloscope
Replace the motor
SCL
Control word watchdog has timed out
The SCL trip indicates that the control word has been enabled and has timed out
30
Recommended actions:
SL.dF
Option module in option slot 1 has changed
The SL.dF trip indicates that the option module in option slot 1 on the drive is a different type to that installed when
parameters were last saved on the drive. The reason for the trip can be identified by the sub-trip number.
Sub-trip
204
Recommended actions:
Turn off the power, ensure the correct option module is installed in the option slot and re-apply the power.
Confirm that the currently installed option module is correct, ensure option module parameters are set correctly and
perform a user save in Pr mm.000.
Unidrive M200 / M201 User Guide
Issue Number: 4
Electrical
Getting
Basic
installation
started
parameters
01
Reserved resettable trip
09
Reserved resettable trip
11 - 12
Reserved resettable trip
14 - 17
Reserved resettable trip
23, 29
Reserved resettable trip
38 - 39
Reserved resettable trip
94 -96
Reserved resettable trip
99
Reserved resettable trip
Reserved resettable trip
Reserved resettable trip
Reserved resettable trip
176
Reserved resettable trip
Reserved resettable trip
Reserved resettable trip
Reserved resettable trip
Reserved resettable trip
234
Reserved resettable trip
Reserved non-resettable trip
249
Reserved resettable trip
Reserved resettable trip
1
No module was installed previously
A module with the same identifier is installed, but the set-up menu for this option slot has been
2
changed, and so default parameters have been loaded for this menu.
A module with the same identifier is installed, but the applications menu for this option slot has been
3
changed, and so default parameters have been loaded for this menu.
A module with the same identifier is installed, but the set-up and applications menu for this option slot
4
have been changed, and so default parameters have been loaded for these menus.
>99
Shows the identifier of the module previously installed.
Running the
NV Media
Optimization
motor
Card
Diagnosis
Description
Reason
Advanced
Technical data
Diagnostics
parameters
UL Listing
193

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive m201

Table of Contents