3.6.2
Enclosure sizing
1. Add the dissipation figures from section 11.1.2 Power dissipation on
page 163 for each drive that is to be installed in the enclosure.
2. If an external EMC filter is to be used with each drive, add the
dissipation figures from section 11.2.1 EMC filter ratings on
page 178 for each external EMC filter that is to be installed in the
enclosure.
3. If the braking resistor is to be mounted inside the enclosure, add the
average power figures from for each braking resistor that is to be
installed in the enclosure.
4. Calculate the total heat dissipation (in Watts) of any other equipment
to be installed in the enclosure.
5. Add the heat dissipation figures obtained above. This gives a figure
in Watts for the total heat that will be dissipated inside the enclosure.
Calculating the size of a sealed enclosure
The enclosure transfers internally generated heat into the surrounding
air by natural convection (or external forced air flow); the greater the
surface area of the enclosure walls, the better is the dissipation
capability. Only the surfaces of the enclosure that are unobstructed (not
in contact with a wall or floor) can dissipate heat.
Calculate the minimum required unobstructed surface area A
enclosure from:
P
-----------------------------------
=
A
(
)
e
k T
T
int
ext
Where:
A
Unobstructed surface area in m
e
T
Maximum expected temperature in
ext
enclosure
T
Maximum permissible temperature in
int
enclosure
P
Power in Watts dissipated by all heat sources in the
enclosure
k
Heat transmission coefficient of the enclosure material
2
o
in W/m
/
C
Example
To calculate the size of an enclosure for the following:
Two drives operating at the Normal Duty rating
External EMC filter for each drive
Braking resistors are to be mounted outside the enclosure
Maximum ambient temperature inside the enclosure: 40°C
Maximum ambient temperature outside the enclosure: 30°C
For example, if the power dissipation from each drive is 187 W and the
power dissipation from each external EMC filter is 9.2 W.
Total dissipation: 2 x (187 + 9.2) =392.4 W
NOTE
Power dissipation for the drives and the external EMC filters can be
obtained from Chapter 11 Technical data on page 159.
The enclosure is to be made from painted 2 mm (0.079 in) sheet steel
having a heat transmission coefficient of 5.5 W/m
front, and two sides of the enclosure are free to dissipate heat.
2
The value of 5.5 W/m
/ºC can generally be used with a sheet steel
enclosure (exact values can be obtained by the supplier of the material).
If in any doubt, allow for a greater margin in the temperature rise.
Unidrive M200 / M201 User Guide
Issue Number: 4
Electrical
Getting
Basic
installation
started
parameters
for the
e
2
2
2
(1 m
= 10.9 ft
)
o
C outside the
o
C inside the
2
o
/
C. Only the top,
Running the
NV Media
Optimization
motor
Card
Figure 3-28 Enclosure having front, sides and top panels free to
dissipate heat
H
Insert the following values:
40 °C
T
int
30 °C
T
ext
k
5.5
P
392.4 W
The minimum required heat conducting area is then:
392.4
-------------------------------- -
=
A
(
e
5.5 40 30
2
= 7.135 m
(77.8 ft
Estimate two of the enclosure dimensions - the height (H) and depth (D),
for instance. Calculate the width (W) from:
A
2HD
------------------------- -
e
=
W
+
H
D
Inserting H = 2m and D = 0.6 m, obtain the minimum
7.135
---------------------------------------------------- -
=
W
2
=1.821 m (71.7 in)
If the enclosure is too large for the space available, it can be made
smaller only by attending to one or all of the following:
Using a lower PWM switching frequency to reduce the dissipation in
the drives
Reducing the ambient temperature outside the enclosure, and/or
applying forced-air cooling to the outside of the enclosure
Reducing the number of drives in the enclosure
Removing other heat-generating equipment
Calculating the air-flow in a ventilated enclosure
The dimensions of the enclosure are required only for accommodating
the equipment. The equipment is cooled by the forced air flow.
Calculate the minimum required volume of ventilating air from:
3kP
-------------------------- -
=
V
T
T
int
ext
Where:
V
Air-flow in m
Maximum expected temperature in °C outside the
T
ext
enclosure
Maximum permissible temperature in °C inside the
T
int
enclosure
P
Power in Watts dissipated by all heat sources in the
enclosure
P
------ -
k
Ratio of
Where:
P
is the air pressure at sea level
0
P
is the air pressure at the installation
I
Typically use a factor of 1.2 to 1.3, to allow also for pressure-drops in
dirty air-filters.
Advanced
Technical data Diagnostics
parameters
D
W
)
2
2
2
) (1 m
= 10.9 ft
)
(
×
×
)
2
2
0.6
+
0.6
3
3
3
per hour (1 m
/hr = 0.59 ft
/min)
o
P
l
UL Listing
width:
35