Safety
Product
Mechanical
information
information
installation
Trip
Oht.I
Inverter over temperature based on thermal model
This trip indicates that an IGBT junction over-temperature has been detected based on a software thermal model.
Control system
Recommended actions:
21
•
Reduce the selected drive switching frequency
•
Ensure Auto-switching Frequency Change Disable (05.035) is set to OFF
•
Reduce duty cycle
•
Increase acceleration / deceleration rates
•
Reduce motor load
•
Check DC bus ripple
•
Ensure all three input phases are present and balanced
Oht.P
Power stage over temperature
This trip indicates that a power stage over-temperature has been detected. From the sub-trip 'xxyzz', the Thermistor
location is identified by 'zz'.
Power system
Recommended actions:
•
Check enclosure / drive fans are still functioning correctly
•
Force the heatsink fans to run at maximum speed
22
•
Check enclosure ventilation paths
•
Check enclosure door filters
•
Increase ventilation
•
Reduce the drive switching frequency
•
Reduce duty cycle
•
Increase acceleration / deceleration rates
•
Reduce motor load
•
Check the derating tables and confirm the drive is correctly sized for the application.
•
Use a drive with larger current / power rating
Oht.r
Rectifier over temperature
The Oht.r trip indicates that a rectifier over-temperature has been detected. The thermistor location can be identified from
the sub-trip number.
Source
Power
system
Recommend actions:
102
•
Check the motor and motor cable insulation with an insulation tester
•
Fit an output line reactor or sinusoidal filter
•
Force the heatsink fans to run at maximum speed by setting Pr 06.045 = 1
•
Check enclosure / drive fans are still functioning correctly
•
Check enclosure ventilation paths
•
Check enclosure door filters
•
Increase ventilation
•
Increase acceleration / deceleration rates
•
Reduce duty cycle
•
Reduce motor load
OI.A1
Analog input 1 over-current
189
Current input on analog input 1 exceeds 24mA.
188
Electrical
Getting
Basic
installation
started
parameters
Source
xx
y
00
1
Source
xx
01
xx
y
Power module
Rectifier
number
number
Running the
NV Media
Optimization
motor
Card
Diagnosis
zz
00
Inverter thermal model gives {Oht.I} trip with sub-trip 0
y
zz
0
zz
Thermistor location in the drive defined by zz
zz
zz
Thermistor location defined by zz
Advanced
Technical data
Diagnostics
parameters
Description
Description
Description
Unidrive M200 / M201 User Guide
Issue Number: 4