Trip
Oht.I
Inverter over temperature based on thermal model
This trip indicates that an IGBT junction over-temperature has been detected based on a software thermal model.
Control system
Recommended actions:
21
Reduce the selected drive switching frequency
Ensure Auto-switching Frequency Change Disable (05.035) is set to OFF
Reduce duty cycle
Increase acceleration / deceleration rates
Reduce motor load
Check DC bus ripple
Ensure all three input phases are present and balanced
Oht.P
Power stage over temperature
This trip indicates that a power stage over-temperature has been detected. From the sub-trip 'xxyzz', the Thermistor
location is identified by 'zz'.
Power system
Recommended actions:
Check enclosure / drive fans are still functioning correctly
Force the heatsink fans to run at maximum speed
22
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Reduce the drive switching frequency
Reduce duty cycle
Increase acceleration / deceleration rates
Reduce motor load
Check the derating tables and confirm the drive is correctly sized for the application.
Use a drive with larger current / power rating
Oht.r
Rectifier over temperature
The Oht.r trip indicates that a rectifier over-temperature has been detected. The thermistor location can be identified from
the sub-trip number.
Source
Power
system
Recommend actions:
102
Check the motor and motor cable insulation with an insulation tester
Fit an output line reactor or sinusoidal filter
Force the heatsink fans to run at maximum speed by setting Pr 06.045 = 1
Check enclosure / drive fans are still functioning correctly
Check enclosure ventilation paths
Check enclosure door filters
Increase ventilation
Increase acceleration / deceleration rates
Reduce duty cycle
Reduce motor load
OI.A1
Analog input 1 over-current
189
Current input on analog input 1 exceeds 24mA.
188
Electrical
Getting
Basic
installation
started
parameters
Source
xx
y
00
1
Source
xx
01
xx
y
Power module
Rectifier
number
number
Running the
NV Media
Optimization
motor
Card
Diagnosis
zz
00
Inverter thermal model gives {Oht.I} trip with sub-trip 0
y
zz
0
zz
Thermistor location in the drive defined by zz
zz
zz
Thermistor location defined by zz
Advanced
Technical data
Diagnostics
parameters
Description
Description
Description
Unidrive M200 / M201 User Guide
Issue Number: 4