Restoring Parameter Defaults; Displaying Parameters With Non-Default Values Only; Displaying Destination Parameters Only; Parameter Access Level And Security - Emerson Quantum MP QMP45A4 User Manual

Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation
5.9

Restoring parameter defaults

Restoring parameter defaults by this method saves the default values in
the drive's memory. (Pr 11.44 (SE14, 0.35) and Pr 11.30 are not affected
by this procedure).
NOTE
Regarding digital I/O control source and restoring parameter defaults:
The base Mentor MP drive defaults to using the 24V digital logic inputs
(terminals 25, 26, 27 and 29) as the drive control inputs. Therefore, if the
drive parameters are restored to default, it will be necessary to
reprogram the parameters listed in the Table 5-5 to restore operation of
the 120 Vac I/O, the procedure is outlined below. It is important that the
24V digital logic input terminals 25, 26, 27, and 29 are not pointed to the
same parameter destinations as the SM-I/O120V module.
Data block 200 if the SMARTCARD that was shipped with the drive
contains the Quantum MP default parameter values that differ from the
Mentor MP default parameter values that differ from the Mentor MP
defaults. These values are also listed in the first two columns of Table 5-
5. Use the following procedure to return the drive to Quantum MP factory
default parameter settings.
Table 5-5 Quantum MP and Mentor MP default parameters
Quantum MP
Parameter
Default
5.16
1
6.40
1
8.22
0.00
8.23
0.00
8.24
0.00
8.26
0.00
9.04
17.06
9.05
1
9.09
0.1
9.10
10.32
9.37
1
17.21
6.39
17.22
6.34
17.23
6.31
17.24
6.33
17.25
10.33
17.28
6.55
Procedure
1. Ensure the drive is not enabled, i.e. terminal 31 is open or Pr 6.15 is
OFF (0)
2. Select USA in Pr xx.00.
3. Either:
Press the red
reset button
Toggle the reset digital input, or
Carry out a drive reset through serial communications by
setting Pr 10.38 to 100 (ensure that Pr. xx.00 returns to 0).
If the SMARTCARD that was shipped with the drive is available:
4. Insert the SMARTCARD into the drive and set Pr xx.00 to 6200.
5. Reset the drive using one of the methods listed in step 3. This will
copy the parameters form SMARTCARD data block 200 to the drive
RAM and drive EEPROM.
If the SMARTCARD is not available:
4. Reprogram the drive parameters listed in Table 5-5 with the values
from the Quantum MP default column
5. Select SAVE in Pr xx.00 to save the parameters to the drive RAM.
6. Reset the drive using one of the methods from step 3.
Quantum MP User Guide
Issue: A3
Electrical
Getting
Basic
Installation
Started
parameters
Mentor MP
Default
0
0
10.33
6.30
6.32
6.31
0.00
0
0.0
0.00
0
0.00
0.00
0.00
0.00
0.00
0.00
www.emersonct.com
Running the
SMARTCARD
Optimization
Motor
Operation
5.10
Displaying parameters with non-
default values only
Select dIS.dEf in Pr xx.00, the only parameters that will be visible to the
user will be those containing a non-default value. This function does not
require a drive reset to become active. To deactivate this function, return
to Pr xx.00 and enter a value of 0.
Please note that this function can be affected by the access level
enabled. You must refer to section 5.12 Parameter access level and
security for more information regarding access level.
5.11
Displaying destination parameters
only
Select dIS.dESt in Pr xx.00, the only parameters that will be visible to
the user will be destination parameters. This function does not require a
drive reset to become active. To deactivate this function, return to
Pr xx.00 and enter a value of 0.
Please note that this function can be affected by the access level
enabled You must refer to section 5.12 Parameter access level and
security for further information regarding access levels.
5.12

Parameter access level and security

The parameter access levels determine whether the user has access to
Menu 0 (in sub block mode) only or to all of the advanced menus (Menus
1 to 23), in addition to Menu 0 (in linear mode).
The user security determines whether the access to the user is read only
or read write.
The user security and the parameter access level can operate
independently of each other as shown in Table 5-6 .
Table 5-6 User security and parameter access levels
Parameter
access level
L1
L1
L2
L2
RW = Read / write access
The default settings of the drive are parameter access level L1 and User
Security Open, i.e. read / write access to Menu 0 with the advanced
menus, not visible
Onboard
Advanced
Technical
PLC
Parameters
Data
User security
Menu 0 status
Open
Sub block RW
Closed
Sub block RO
Open
Linear RW
Closed
Linear RO
RO = Read only access
UL
Diagnostics
Information
Advanced
menus status
Not visible
Not visible
RW
RO
61