Electrical Installation; Power Connections - Emerson unidrive m200 User Manual

Hide thumbs Also See for unidrive m200:
Table of Contents

Advertisement

Safety
Product
Mechanical
information
information
installation
4

Electrical installation

Many cable management features have been incorporated into the
product and accessories, this chapter shows how to optimize them. Key
features include:
Internal EMC filter
EMC compliance with shielding / grounding accessories
Product rating, fusing and cabling information
Brake resistor details (selection / ratings)
Electric shock risk
The voltages present in the following locations can cause
severe electric shock and may be lethal:
AC supply cables and connections
WARNING
DC and brake cables, and connections
Output cables and connections
Many internal parts of the drive, and external option units
Unless otherwise indicated, control terminals are single
insulated and must not be touched.
Isolation device
The AC and / or DC power supply must be disconnected
from the drive using an approved isolation device before any
cover is removed from the drive or before any servicing work
WARNING
is performed.
STOP function
The STOP function does not remove dangerous voltages
from the drive, the motor or any external option units.
WARNING
Stored charge
The drive contains capacitors that remain charged to a
potentially lethal voltage after the AC and / or DC power
supply has been disconnected. If the drive has been
WARNING
energized, the AC and / or DC power supply must be
isolated at least ten minutes before work may continue.
Normally, the capacitors are discharged by an internal
resistor. Under certain, unusual fault conditions, it is possible
that the capacitors may fail to discharge, or be prevented
from being discharged by a voltage applied to the output
terminals. If the drive has failed in a manner that causes the
display to go blank immediately, it is possible the capacitors
will not be discharged. In this case, consult Control
Techniques or their authorized distributor.
Equipment supplied by plug and socket
Special attention must be given if the drive is installed in
equipment which is connected to the AC supply by a plug
and socket. The AC supply terminals of the drive are
WARNING
connected to the internal capacitors through rectifier diodes
which are not intended to give safety isolation. If the plug
terminals can be touched when the plug is disconnected
from the socket, a means of automatically isolating the plug
from the drive must be used (e.g. a latching relay).
Unidrive M200 / M201 User Guide
Issue Number: 4
Electrical
Getting
Basic
Running the
installation
started
parameters
NV Media
Optimization
motor
Card
4.1

Power connections

4.1.1
AC and DC connections
Figure 4-1 Size 1 power connections
PE
L
L2-N
Optional EMC
filter
Optional
line reactor
Fuses
L1
L2-N
Mains
Supply
Supply
Ground
See Figure 4-7 Size 1 to 4 ground connections (size 2 shown) on
page 48 for further information on ground connections.
Figure 4-2 Size 2 power connections
PE
L1
L2
L3
Optional EMC
filter
Optional
line reactor
Fuses
L1
L2
L3
Mains
Supply
Supply
Ground
See Figure 4-7 Size 1 to 4 ground connections (size 2 shown) on
page 48 for further information on ground connections.
Advanced
Technical data
Diagnostics
parameters
+
BR
U
V
W
Thermal
overload
protection
device
Optional
braking
resistor
Motor
Optional ground
connection
U
V
W
Thermal
overload
protection
device
Motor
Optional ground
connection
UL Listing
+
BR
Optional
braking
resistor
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive m201

Table of Contents