Top Control variants

3.3
The Top Control positioner is available in 3 forms, varying in electrical connection and control functions.
Multipole connection with complete functions (Fig. 3.8)
Terminal with PG cable glands and terminals with restricted functions (Fig. 3.9)
QUICKON connection with restricted functions
External setpoint for posi-
tion or process control
4..20 mA
0..20 mA
0..10 V
0..5 V
Process control value
4..20 mA
Frequency
Pt 100
Binary input
24 V DC
Pt 100
Fig. 3.8: Position interface with multipole connections
External setpoint for posi-
tion or process control
4..20 mA
0..20 mA
0..10 V
0..5 V
Process control value
4..20 mA
Frequency
Pt 100
Binärer Eingang
24 V DC
Pt 100
Fig. 3.9: Position interface with cable glands
NOTE
The positioners in the Top Control range posses 3-wires instruments. The 24 V DC power supply is isolated from
the setpoint signal.
80
Positioner
Top Control
(Multipole
connection)
Operating
Positioner
Top Control
(PG cable glands)
Operating
2 binary output
Analogue position feedback
Limit switch 1 + 2
2 binary output
Analogue position feedback
Initiatoren 1 + 2
Advice:
Choose between an analogue
position feedback and two binary
outputs by setting the jumper.