Configuration within the MAIN menu:
ACTFUNC
INPUT
ADDFUNCT
X.TUNE
END xx
Entry of the setpoint within the AUTOMATIC mode
After the configuration the Top Control acts as a position controller.
Enter the setpoint as a signal input.
Switch between the display possibilities:
Message on display:
•
Actual position of the actuator
•
Setpoint of the actuator
•
Signal entry for the setpoint
(equivalent to setpoint)
•
Internal temperature of the positioner
Manual opening and closing of the valve within the MANUAL mode
Open the valveantriebs:
Close the valveantriebs:
Message on display:
Advice Select the POS_xxx display, to ensure that the actual position of the actuator is displayed.
NOTE
Top Control Positioner
Function of the actuator
FUNC SNGL
- single acting
FUNC DOUB
- double acting
Selection of the input signal
INP 420A
- Current 4..20 mA
INP 020A
- Current 0..20 mA
INP 010V
- Voltage 0..10 V
INP 05V
- Voltage 0..5 V
Omit for quick commissioning
Activation of the self-calibration (Fig. 4.4).
Return to the AUTOMATIC mode. The message EEPROM is displayed until the new parameters
are stored.
POS__xxx (0..100%)
CMD__xxx (0..100%)
INP__xxx (0..100%)
TEMP_xx.x (in °C)
The previous display within the AUTOMATIC mode remains active.
87