Set Safety Position And Effective Direction; Adjustment Of Position Control On Ag2 - Burkert AE3323 Quick Start Manual

Electromotive diaphragm valve
Hide thumbs Also See for AE3323:
Table of Contents

Advertisement

Available languages

Available languages

9.2
Set safety position and effective
direction
The effective direction and safety position are set using DIP
switches 1 and 2.
DIP switch 2
Set-point value
(0...5 V)
(10...30 V)
Log 0
Log 1
Valve
NC
OFF
Valve open
closed
Valve
NO
ON
Valve open
closed
Tab. 16: Set effective direction and safety position
34
DIP switch 1
Switch
Safety
position
position
(safety
position
enabled/
disabled)
ON
Valve closed
none
OFF
(actuator
stops)
ON
Valve open
none
OFF
(actuator
stops)
English
Type 3323, 3324, 3325
Start-up
9.3

Adjustment of position control on AG2

When executing the function M.Q0.TUNE the position control is
adjusted at the physical stroke of the proportional valve in use
and the required closing force is determined.
To this end, the seal closure point must be approached manually.
It is important that the valve is not entirely closed. Based on this
position the device uses an algorithm to calculate the optimum
force for sealing.
Seal closure point: position where the valve is
End position
Stroke
Fig.27:
Seal closure point
almost seal-tight.