Power supply (circular connector M12)
Pin
Assignment
1
+ 24 V
2
not connected
3
GND
4
not connected
Limit switches (circular connector M8)
Pin
Assignment
1
Limit switch 1 +
2
Limit switch 1 GND
3
Limit switch 2 +
4
Limit switch 2 GND
Process value (circular connector M8)
Signal *
4..20 mA
- internal power
supply
4..20 mA
- external power
supply
Frequency
-internal power
supply
Frequency
-external power
supply
Pt-100
* Connectable through software (see 6.3.2)
ATTENTION!
A screw with a nut is available in the connecting module for connection of the technical earth (TE). In order
to comply with the EMC requirements connect this screw to a good earthing point with a short length cable
(max. 30 cm).
90
Pin
Assignment
1
+ 24 V transmitter entry
2
Transmitter output
3
GND
4
Strap to GND
1
not connected
2
Analogic signal +
3
not connected
4
Analogic signal -
1
+24 V supply of sensor
2
Pulse +
3
GND
4
Pulse -
1
not connected
2
Pulse +
3
not connected
4
Pulse -
1
not connected
2
Process 1
3
Process 3
4
Process 2
External connection
24 V DC ± 10 %
Residual ripple 10 %
External connection
Jumper
External connection
1
3
2
4
3
4
2
Transmitter
+24 V
GND
Puls +
Puls -
Puls +
Puls -
Pt 100