5 Installation Procedure
Use only a MECHATROLINK-III dedicated communication cable. Refer to
more information.
Note:
Maximum transmission distance is 100 m (328 ft). Minimum wiring distance between stations is 0.2 m (7.9 in).
■
Option Connection Diagram
*1
Connect the MECHATROLINK-III cable to connector CN1 or CN2.
*2
Connect the provided ground wire for installations on 1000-series drives and GA500 drives.
The ground wire is not necessary for installation on GA700, GA800, CR700, or CH700 drives.
■
Communication Cable Topology
The dual communication cable ports on the option board act as a switch to allow for
flexibility in cabling topology. Users may employ a traditional star network topology
using a single communication cable port on the option. Users may also choose to employ
a ring topology using both communication cable ports on the option and reduce the
requirements of MECHATROLINK-III hub module ports.
28
Figure 5.14 Option Connection Diagram
YASKAWA TOEP C730600 88A MECHATROLINK-III Installation Manual
Table 5.1