Selection Of Operation Mode - Toshiba TOSVERT VF-PS1 Instruction Manual

High performance inverter
Hide thumbs Also See for TOSVERT VF-PS1:
Table of Contents

Advertisement

Frequency setting with operation panel and operation with terminal board
This setting is used to set the frequency using the operation panel and to perform operation control using the terminal
board.
Use the
and
In sink logic mode: PWR-P24/PLC ON: Standby (ON (short-circuited) by default),
F-CC ON: Forward run, R-CC ON: Reverse run.
Frequency setting and operation with operation panel (
This setting is used to set the frequency and to perform operation control, using the operation panel.
Use the
and
Use the
and
RUN
Coast stop (
= )
This setting is used to coast and stop the motor by means of an S3 terminal signal.
The frequency is adjusted according to the setting of the parameter
setting of the parameter
If S3 and CC are short-circuited, the motor will be put into a standby state. If the circuit between S3 and CC is opened, the
motor coasts and stops.
5.5

Selection of operation mode

5
• Function
These parameters are to program which command to the inverter (from operation panel, terminal board, remote
input device or options) will be given priority in running/stopping the operation and in frequency setting (speed).
<Command mode selection>
[Parameter setting]
Title
[Programmed value]
:
Terminal board operation
:
Operation panel operation
:
2-wire RS485 communication operation
:
4-wire RS485 communication operation
:
Communication option input enabled
* There are two types of function: the function that conforms to commands selected by
function that conforms only to commands from the terminal board.
⇒ Refer to the table of input terminal function selection in Section 7.2.
* When priority is given to commands from a linked computer or terminal board, they have priority over the setting of
.
keys to set the frequency.
keys to set the frequency.
keys to perform operation control.
STOP
.
: Command mode selection
: Frequency setting mode selection 1
Function
:Terminal input enabled
:Operation panel input enabled (including LED/LCD option input)
Command
:2-wire RS485 communication input
mode selection
:4-wire RS485 communication input
:Communication option input
ON and OFF of an external signal Runs and stops operation.
Press the
a run. (including LED/LCD option input)
= )
. The motor is operated in accordance with the
Adjustment range
RUN
STOP
and
keys on the operation panel to Run and stop
Run and stop commands are entered from the 2-wire
RS485 communications device.
(Communication No.: FA00)
Run and stop commands are entered from the 4-wire
RS485 communications device.
(Communication No.: FA04)
Signals from an optional communication device are used to
start and stop operation.
⇒ For details, refer to Instruction Manual (E6581281,
E6581343, E6581288) specified in Section 6.36.
E-6
E6581531
Default setting
, and the