Calorific values of the inverter and the required ventilation
The energy loss when the inverter converts power from AC to DC and then back to AC is typically about 2.5% to 5%.
In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of the
cabinet must be ventilated and cooled.
The amount of forced air-cooling ventilation required and the necessary heat exchange surface area when operating
in a sealed cabinet according to motor capacity are as follows.
Voltage
class
1
VFPS1-5022PM
VFPS1-5030PM
VFPS1-5040PM
VFPS1-5055PM
VFPS1-5075PM
VFPS1-6030PL
VFPS1-6055PL
VFPS1-6075PL
VFPS1-6110PL
VFPS1-6150PL
VFPS1-6185PL
VFPS1-6220PL 18.5kW 25Hp
VFPS1-6300PL
VFPS1-6370PL
VFPS1-6450PL
VFPS1-6550PL
VFPS1-6750PL
VFPS1-6900PL
VFPS1-6110KPC
VFPS1-6132KPC 110kW 150Hp 132kW
VFPS1-6160KPC 132kW
VFPS1-6200KPC 160kW 200Hp 200kW
VFPS1-6250KPC 185kW 250Hp 250kW
VFPS1-6315KPC 250kW 350Hp 315kW
VFPS1-6400KPC 315kW 450Hp 400kW
VFPS1-6500KPC 400kW 550Hp 500kW
VFPS1-6630KPC 500kW 700Hp 630kW
Note1: The heat loss for the external options (input reactor, radio noise reduction filters, etc.) is not included in the
calorific values in the table.
Note2: Each calorific value in the table refers to the quantity of heat that an inverter produces when it is operated
continuously at the factory default
Calorific
Applicable Motor
values
500V
600V
690V
2.2kW
3Hp
3kW
-
4kW
5Hp
5.5kW
7.5Hp
7.5kW
10Hp
2.2kW
3kW
3Hp
4kW
5.5kW
5Hp
5.5kW
7.5kW
7.5Hp
7.5kW
11kW
10Hp
11kW
15kW
15Hp
15kW
18.5kW
20Hp
22kW
22kW
30kW
30Hp
30kW
37kW
40Hp
37kW
45kW
50Hp
45kW
55kW
1087
60Hp
55kW
75kW
1545
75Hp
75kW
90kW
1947
100Hp
90kW
125Hp 110kW
2320
2750
160kW
3290
-
4030
5160
6310
7550
9660
11950
(carrier frequency) under a load factor of 100%.
Amount of forced air cooling
ventilation required
3
(W)
(m
/min)
100
0.57
118
0.68
143
0.82
183
1.1
244
1.4
119
0.68
158
0.91
182
1.1
227
1.3
300
1.8
386
2.3
463
2.7
556
3.2
716
4.1
911
5.2
6.2
8.9
11.1
13.3
15.7
18.8
23.0
29.5
36.0
43.1
55.1
68.2
A-28
E6581531
Heat exchange surface area
required for sealed storage
cabinet
2
(m
)
2.0
2.4
2.9
3.7
4.9
2.4
3.2
3.7
4.6
6.0
7.8
9.3
11.2
14.4
18.3
21.8
30.9
39.0
46.4
55.0
65.8
80.6
104
127
151
194
239