Extended Parameters; Input/Output Parameters; Low-Speed Signal - Toshiba TOSVERT VF-PS1 Instruction Manual

High performance inverter
Hide thumbs Also See for TOSVERT VF-PS1:
Table of Contents

Advertisement

6. Extended parameters

Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes.
⇒ Refer to Section 11, Table of parameters.
6.1

Input/output parameters

6.1.1 Low-speed signal

: Low-speed signal output frequency
• Function
When the output frequency exceeds the setting of
used as an electromagnetic brake excitation/release signal.
Through the open collector terminal OUT1 or OUT2 (24Vdc-50mA [max.]).
[Parameter setting]
Title
Output frequency [Hz]
Low-speed signal output
P24-OUT1 terminals (Default setting)
P24-OUT2 terminals
FLA-FLB-FLC terminals
Low-speed signal output: Inverted
[Connection diagram (Sink logic)]
• Output terminal setting
The low-speed signal (ON signal) output function has been assigned to the terminal OUT1 by default. This
setting must be changed to invert the polarity of the signal.
[Parameter setting]
Title
Note: To put out signals to OUT2, select the parameter
Function
Low-speed signal output frequency
Set frequency
0
Ry
NO
CC
Function
Output terminal function selection
1(OUT1)
an ON signal will be generated. This signal can be
Adjustment range
~
Hz
P24
OUT1 (or OUT2)
Adjustment range
~
.
F-1
E6581531
Default setting
Time [s]
ON
OFF
ON
OFF
Example of setting
(ON signal) or
(OFF signal)
6