9.2.3 Caution as to peripheral devices

When installing a no-fuse circuit breaker or a fuse box on the primary side of the inverter, use UL-certified one.
The UL certification test on this inverter was conducted under the power supply short-circuit current* conditions
shown in Table 4 (*: current that flows in the event of a short-circuit in the power supply). Note that power supply
short-circuit currents vary depending on the capacity of the motor used.
Input voltage
Applicable motor
(V)
(kW)
1.5~90
110,132
600
160~315
400~630
Applicable
motor
Inverter model
HP
KW
VFPS1-5022PM
3
2.2
VFPS1-5040PM
5
4
VFPS1-5055PM
7.5
5.5
VFPS1-5075PM
10
7.5
VFPS1-6150PL
15
11
VFPS1-6185PL
20
15
VFPS1-6220PL
25
18.5
VFPS1-6300PL
30
22
VFPS1-6370PL
40
30
VFPS1-6450PL
50
37
VFPS1-6550PL
60
45
VFPS1-6750PL
75
55
VFPS1-6900PL
100
75
VFPS1-6110KPC
125
90
VFPS1-6132KPC
150
110
VFPS1-6200KPC
200
160
VFPS1-6250KPC
250
185
VFPS1-6315KPC
350
250
VFPS1-6400KPC
450
315
VFPS1-6500KPC
500
400
VFPS1-6630KPC
700
500
*1: UL output current is different from unit rating output current.
*2: The cables used must be 75°C copper cables within 40°C ambient temperature.

9.2.4 Caution as to the protection of motors from overload

When using the inverter's thermal protection function to protect the motor from overload, read the instruction
manual included with the inverter carefully and set parameters according to the specifications of the motor used.
When using the inverter to control the operation of multiple motors, install an overload relay for each individual
motor.
Table 4
Power supply short-circuit current and maximum input voltage
Suitable for use on a circuit capable of delivering not more than 22,000 rms
symmetrical amperes in below, 600 volts maximum.
Suitable for use on a circuit capable of delivering not more than 28,000 rms
symmetrical amperes in below, 600 volts maximum.
Suitable for use on a circuit capable of delivering not more than 35,000 rms
symmetrical amperes in below, 600 volts maximum.
Suitable for use on a circuit capable of delivering not more than 42,000 rms
symmetrical amperes in below, 600 volts maximum.
Table 5
AIC, Fuse and Wire sizes
UL
AIC (A)
output current
(Interrupting
(A) *1
capacity)
3.9
22000
6.1
22000
9.0
22000
11.0
22000
17.0
22000
22.0
22000
27.0
22000
32.0
22000
41.0
22000
52.0
22000
62.0
22000
77.0
22000
99.0
22000
125
100000
144
100000
192
100000
242
100000
336
100000
412
100000
528
100000
672
100000
I-5
Power supply short-circuit current (A)
Input wire
UL-fuse 600V class
sizes of
and current
power circuit
(A)
*2
Class J 15A max
AWG14
Class J 25A max
AWG14
Class J 30A max
AWG12
Class J 35A max
AWG10
Class J 35A max
AWG8
Class J 45A max
AWG8
Class J 60A max
AWG6
Class J 60A max
AWG4
Class J 90A max
AWG3
Class J 110A max
AWG2
Class J 125A max
AWG2
Class J 150A max
AWG1/0
Class J 200A max
AWG2/0
Class J 200A max
AWG2/0
Class J 200A max
AWG3/0
Class J 300A max
250MCM
Class J 400A max
2X250MCM
Class J 500A max
2X350MCM
Class J 2x300A max
3X300MCM
Class J 2x400A max 2X(2X300MCM) 4X300MCM
Class J 2x500A max 2X(2X400MCM) 4X400MCM
E6581531
Output wire
sizes of
Earth
power circuit
*2
*2
AWG14
AWG14
AWG14
AWG14
AWG14
AWG14
AWG14
AWG12
AWG10
AWG8
AWG8
AWG10
AWG6
AWG10
AWG4
AWG10
AWG3
AWG8
AWG8
AWG2
AWG2
AWG8
AWG1/0
AWG6
AWG2/0
AWG6
AWG6
AWG2/0
AWG3/0
AWG2
250MCM
AWG2
2X250MCM
AWG1
AWG2/0
2X350MCM
AWG3/0
3X300MCM
AWG4/0
AWG4/0