Toshiba TOSVERT VF-PS1 Instruction Manual page 248

High performance inverter
Hide thumbs Also See for TOSVERT VF-PS1:
Table of Contents

Advertisement

1. Basic parameter [3/4]
Communication
Title
Function
No.
Motor electronic thermal protection
0600
level 1
Electronic thermal protection
0017
characteristic selection
0701
Current/voltage unit selection
0005
FM terminal meter selection
0006
FM terminal meter adjustment
0670
AM terminal meter selection
0671
AM terminal meter adjustment
0300
PWM carrier frequency
0301
Auto-restart control selection
Regenerative power ride-through
0302
control
0304
Dynamic braking selection
0308
Dynamic braking resistance
Allowable continuous braking
0309
resistance
*1: ⇒ For the adjustment range, see the table on page K-39.
*2: For 37kW and above, the carrier frequency is between 2.5 and 4.9kHz inclusive..
*3: Default values vary depending on the capacity. ⇒ See the table of K-47.
*4: Default setting value is adjusted for connection of frequency meters "QS60T". (Between FM and CCA: Approx. 3.6V) (Between AM and CCA: Approx. 3.6V)
Adjustment range
10~100%
Overload
Setting
Motor type
OL stall
protection
0
○ (protect)
× (not stall)
1
○ (protect)
○ (stall)
Standard
× (not
2
× (not stall)
Motor
protect)
× (not
3
○(stall)
protect)
4
○ (protect)
× (not stall)
5
○ (protect)
○(stall)
× (not
VF Motor
6
× (not stall)
protect)
× (not
○(stall)
7
protect)
0:%
1:A (ampere)/V (volt)
0~76 *1
-
0~76 *1
-
2.5~6.0kHz (2.5~4.9kHz) *2
0:Disabled
1:At auto-restart after momentary stop
2:When turning ST on or off
3:1+2
4:At start-up
0:Disabled
1:Power ride-through
2:Deceleration stop during power failure
0:Deselect
1:Enabled (braking resistance overload detect)
2:Enabled (braking resistance overload not detect)
0.5~1000Ω
0.01~600.0kW
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Default setting
Write
setting unit
during
(Panel/Communi
=
=
=
running
cation)
500V
575V
690V
-50Hz
-60Hz
-50Hz
1/1
100
100
100
Enabled
0
0
0
0
Enabled
0
0
0
1/1
Enabled
1/1
0
0
0
Enabled
1/1
*4
*4
*4
Enabled
2
2
2
1/1
Enabled
1/1
*4
*4
*4
Enabled
0.1/0.1
*3
*3
*3
Enabled
1/1
0
0
0
Disabled
0
0
0
1/1
Disabled
1/1
0
0
0
Disabled
0.1/0.1
*3
*3
*3
Disabled
*3
*3
*3
0.01/0.01
Disabled
Vector
V/f
Reference
control
●/●
5. 14
●/●
5. 14
●/●
5. 15
●/●
5. 16
●/●
5. 16
●/●
5. 16
●/●
5. 16
●/●
5. 17
●/●
5. 18.1
●/●
5. 18. 2
●/●
5. 19
●/●
5. 19
●/●
5. 19

Advertisement