IFM Electronic CR0403 Programming Manual page 54

Hide thumbs Also See for CR0403:
Table of Contents

Advertisement

ifm
Programming Manual
ecomatmobile
Configurations
>
Binary outputs: configuration and diagnosis
The following operating modes are possible for the device outputs (→ data sheet):
• binary output, plus switching (BH) with/without diagnostic function
Basic circuit of binary output plus switching (BH)
for positive output signal
► Configuration of each output is made via the application program:
OUTPUT
→ FB
(→ page 180)> input MODE.
WARNING
Dangerous restart possible!
Risk of personal injury! Risk of material damage to the machine/plant!
If in case of a fault an output is switched off via the hardware, the logic state generated by the
application program is not changed.
► Remedy:
• Reset the output logic in the application program!
• Remove the fault!
• Reset the outputs depending on the situation.
>
Configuration of the output diagnosis
If the diagnosis is to be used, it needs to be activated additionally.
► If using the output as binary output with diagnosis (→ data sheet):
→ FB OUTPUT > input MODE = 15 or 18
>
OUTPUT
The FB
(→ page 180) provides the diagnostic messages of the outputs on its RESULT
output.
BasicController (CR0403) Runtime System V03.02
Qn = pin output n
(L) = load
Function configuration of the inputs and outputs
54
2015-04-01