3.3.1 SETUP MENU (CONTINUED)
NAME/CODE
DESCRIPTION
UPDATE
Display Update Rate: Selects the time between display updates.
(UR)
The motion detector can be made more sensitive to small
changes by increasing the update time, according to the
operator's preference.
ZERO KY
ENABLE or DISABLE the Zero key. The LZ1 or LZ0 EDP com-
(LZ)
mands will be accepted at any time. However, different locks are
set or reset depending on whether the indicator is in SETUP or
OPERATE mode. If either lock is on, the key is disabled.
TARE KY
ENABLE or DISABLE the Tare key. The LT1 or LT0 EDP com-
(LT)
mands will be accepted at any time. However, different locks are
set or reset depending on whether the indicator is in SETUP or
OPERATE mode. If either lock is on, the key is disabled.
UNIT KY
ENABLE or DISABLE the Units key. The LU1 or LU0 EDP com-
(LU)
mands will be accepted at any time. However, different locks are
set or reset depending on whether the indicator is in SETUP or
OPERATE mode. If either lock is on, the key is disabled.
PRNT KY
ENABLE or DISABLE the Print key. The LP1 or LP0 EDP com-
(LP)
mands will be accepted at any time. However, different locks are
set or reset depending on whether the indicator is in SETUP or
OPERATE mode. If either lock is on, the key is disabled.
KEYBRD
ENABLE or DISABLE all front panel keys. The LK1 or LK0 EDP
(LK)
commands will be accepted at any time. However, different locks
are set or reset depending on whether the indicator is in SETUP
or OPERATE mode. If either lock is on, the front panel keys are
disabled (while in OPERATE mode).

3.3.2 DIGITAL INPUT MENU

Up to two external switches can be wired into the digital input connections on the J4 termi-
nal of the main board (See Figure 8). Each switch can be programmed to duplicate the
normal functions of any front panel key. For instance, a switch could remotely "press" the
PRINT key through a digital input channel. The switches could also be programmed to
perform Lock Keyboard or Hold/Clear functions. The KEY LK (Keyboard Lockout) selection
locks out the key functions in the normal operation mode. These are the Zero, Gross/Net,
etc., key functions. It does not lock the keys in the Setup Mode. The HLD CLR (Hold/
Clear) selection for Input 2 holds the display and clears the running average filter. The
Print function and EDP commands XG, XN and XT process the Hold values. The continu-
ous serial output continues, sending the weight and status information captured when the
Hold/Clear function was initiated.
NAME/CODE
DESCRIPTION
Duplicates function of ZERO key
DIGIN 1
Duplicates function of GROSS/NET key
(IA)
Duplicates function of TARE key
Duplicates function of UNITS key
DIGIN 2
Duplicates function of PRINT key
(IB)
Duplicates function of TEST key
Locks out keyboard (IA only)
Holds display and clears running average filter (IB only)
20
CODE/VALUE
0 = 250ms
5 = 2 sec
1 = 500ms 6 = 2.5sec
2 = 750ms 7 = 3 sec
3 = 1 sec
8 = 4 sec
4 = 1.5 sec
0 = ENABLE
1 = DISABLE
0 = ENABLE
1 = DISABLE
0 = ENABLE
1 = DISABLE
0 = ENABLE
1 = DISABLE
0 = ENABLE
1 = DISABLE
CODE/SELECTION
0 = ZERO
1 = GROSS/NET
2 = TARE
3 = UNITS
4 = PRINT
5 = TEST
6 = LOCK KEYBD (IA)
6 = HOLD/CLEAR (IB)

Hide quick links: