Operation
Occurs When
Mode
Silenced
An alarm or
trouble condition
has been
silenced but still
exists. To silence
alarms and
troubles, press
SILENCE
followed by the
Installer or User
Code, if
necessary.
10.6.1 Multi-Site Annunciator and Multi-Site User Access
Multi-site Annunciators are unique as they can display the status and event history of all sites they are assigned to. These displays can be
especially useful in guard shacks or security centers. A multi-site display is indicated by the words "Multi-Site Display" at the top of the
idle screen.
1.
The ACK, DRILL, RESET and F-Macro keys are disabled until a multi-site user access code has been entered and a specific site
has been selected.
2.
Multi-site Annunciator silencing rules:
• If any of the assigned sites are silenced, the Silenced LED will be lit.
• Silence key will only silence the sound from the multi-site annunciator on which the silence key was pressed. This is called
being Locally Silenced. If Locally Silenced is enabled on a multi-site annunciator, it will be indicated by a blinking Silenced
LED.
• If any new troubles, supervisory, pre-alarms, or alarms are triggered in any assigned sites, locally silenced annunciators will re-
sound.
• If a multi-site annunciator is locally silenced for 4 or 24 hours depending on user selection, the locally silenced annunciators will
re-sound.
3.
The IFP-300/ECS menu system is disabled on a multi-site annunciator. Pressing the Right or Enter keys will bring you straight into
event history for assigned sites. To get into the menu system, a multi-site user password must be entered and then a site must be
selected from the site selection menu. Once this is done you will have access to the idle screen of that site and the annunciator will
temporarily act like a single site annunciator.
4.
A multi-site annunciator will sound the highest priority tone from the sites it is assigned to.
NOTE: A multi-site display is created in Module programming in the edit properties menu for an annunciator. See section 9.2.1.
NOTE: An annunciator cannot be programmed as a multi-site display when it is associated with an ECS-VCM, ECS-NVCM or ECS-RVM in a
ECS system.

10.7 Releasing Operations

The control panel supports two types of releasing: Double Interlock Zone, and Single Interlock Zone. The Double Interlock Zone opera-
tion requires an interlock switch input in the system, and the Single Interlock Zone does not. An interlock switch is typically a dry-con-
tact pressure switch.
When Single or Double Interlock Zone releasing is selected using HFSS Honeywell Fire Software Suite, the software suite will automat-
ically default the following system parameters:
NOTE: The defaults created can be modified through programming if desired.
Output Group 2 is created. Output Group 2 will be defaulted as a "Detector Alarm" output group for all releasing zones. NAC
[98:001] is assigned to Output Group 2.
Output Group 3 is created. Output Group 3 will be defaulted as a "Interlock Release Alert" output group for all releasing zones.
NAC [98:002] is assigned to Output Group 3.
Output Group 4 is created. Output Group 4 will be defaulted as "Interlock Release Alarm" output group for all releasing zones.
NAC circuit [98:003] is assigned to Output Group 4.
NOTE: The installer must define which input points will be used for detectors, manual release switches, or interlock/pressure switches.
NOTE:
For manual release operation, Installer must use an FM approved/ UL listed releasing manual station.
143
System Behavior
SYSTEM SILENCE LED is on. SYSTEM
TROUBLE, SUPERVISORY and/or GENERAL
ALARM LED (depending on condition) is on.
The annunciator (and any notification devices
attached to the system) will be silenced.
Table 10.2 Operations Mode Behavior
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
In This Mode You Can
Press down arrow to view the location of the
alarm, supervisory or trouble. When the condition
no longer exists, the SYSTEM SILENCED and
SYSTEM TROUBLE LED, SUPERVISORY and/or
GENERAL ALARM LEDs turn off.