Temperature Controller Configuration Record Sheet - Honeywell BCS 3600 Operating Instructions Manual

Burner control system
Table of Contents

Advertisement

Head 1
OUT
F
C
or
MAN
A
or
SP
Keys and functions
Changing the setpoints
1 Press the [LOWER DISPLAY] key until SP and the current setpoint
appears in the lower display.
2 Press and hold the ▲ key to increase the set point value. To make
changes more quickly, press the ▼ key while holding ▲ key. This
will shift the changing digit one place to the left.
3 To decrease the set point value, reverse the above procedure.
Adjusting the burner firing rate in the manual mode
1 Press the [AUTO/MANUAL] key to place the Controller in the
Manual Mode. The MAN indicator will come on and the lower
display will automatically change to show % OUT.
2 Press and hold the ▲ key to increase % Output value. To make
changes more quickly press the ▼ key while holding ▲ key. This
will shift the changing digit one place to the left.
3 To decrease the % Output value, reverse the above procedure.
Head 2
Indicates control relay 1 and/or
2 on.
Indicated either degrees
Fahrenheit or Centigrade.
Indicates either Manuel or Auto
mode.
Indicates local setpoints #1.
Also, a bar is lighted when the
setpoint being used is shown
on the lower display.
Selects functions within each
configuration group
Scrolls through the
configuration groups.
Returns controller to normal
display from Set Up mode.
Toggles various operating
parameters for display.
Increases setpoints or output
value. Increases the
configuration values or
changes functions in
configuration mode groups.
Infrared tranceiver
Selects Manual or Auto mode.
Hold key down to cycle
through configured setpoints.
Enables Run/Hold of the SP
ramp or program plus timer
start.
Decreases setpoint or output
value. Decreases the
configuration values or
changes functions in
configuration mode groups.
NEMA 4x and IP66 screw
attachment (each corner).
teMPeRAtURe ContRoLLeR ConFIGURAtIon
ReCoRD sHeet
LoWeR
set UP
DIsPLAY
GRoUP
(FUnnCtIon)
PROP BD
RATE MIN
RESET RPM
SECURITY
TUNING
LOCKOUT
AUTO MAN
RUN HOLD
SP SEL
SP RAMP
SP RAMP
SP RATE
FUZZY
ACCUTUNE
ACCUTUNE
CONT ALG
ALGORITHM
TIMER
IN ALG1
OUT ALG
OUT ALG
MOTOR TI
IN 1 TYPE
IN 1 HIGH
IN 1 LOW
INPUT 1
RATIO 1
BIAS IN 1
FILTER 1
BURNOUT 1
INPUT 2
IN 2 TYPE
PV SOURCE
PID SETS
CONTROL
LSP'S
RSP SRC
SP TRACK
PWR MODE
SP HI LIMIT
SP LO LIMIT
ACTION
OUT RATE
OUT HI LIM
OUT LO LIM
I HI LIM
CONTROL
I LO LIM
cont.
DROPOFF
DEADBAND
FAILSAFE
FAILMODE
MAN OUT
AUTO OUT
PB OR GAIN
MIN OR RPM
COM ADDR
COMSTATE
COM
IRENABLE
BAUD
TX DELAY
A1S1 TYPE
A1S2 TYPE
A2S1 TYPE
A2S2 TYPE
ALARM HYST
ALARMS
BLOCK
DIAGNOST
A1S1 VALUE
A2S1 VALUE
A2S2 VALUE
DECIMAL
TEMPUNIT
DISPLAY
PWR FREQ
LANGUAGE
7
FACtoRY
FInAL
ConFIGURAtIon
settInG
15.00
0.00
1.00
0
NONE
ENABLE
DISABLE
ENABLE
DISABLE
DISABLE
DISABLE
DISABLE
PID A
DISABLE
NONE
POSITN
40
J TC L
550.0 F
20.00 F
1.000
0.0
1
UP
SLIDEW
INPUT 1
1 ONLY
1 ONLY
NONE
NONE
MANUAL
550.0 F
20.00 F
REVERSE
DISABLE
100.0
0.0
100.0
0.0
0.0
2.0
0.0
NO LATCH
0.0
0.0
PB PCT
RPM
3
DISBALE
ENABLE
19200
1
NONE
NONE
NONE
NONE
0.1
DISABLE
DISABLE
Not Applicable
Not Applicable
Not Applicable
NONE
DEG F
60 HZ
ENGLISH