Installation
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
•
2 ANN-80 Remote LCD Annunciators
•
1 ANN-S/PG Serial/Parallel Printer Interface Module
•
1 ANN-I/O LED Driver Module
The total worst case current is calculated as follows:
ANN-80 Current Draw
ANN-S/PG Current Draw
ANN-I/O Current Draw
Using this value and referring to the Wiring Distance Table 2.1 on page 31, it can be found that
the available options are:
2.7.1.2 Wiring Configuration
Figure 2.15 illustrates the wiring between the FACP and ANN-BUS devices.
32
Total Worst Case Current Draw
463 feet maximum using 22 Gauge wire
1,172 feet maximum using 18 Gauge wire
1,866 feet maximum using 16 Gauge wire
2,953 feet maximum using 14 Gauge wire
TB3
Figure 2.15 FACP wiring to ANN-BUS Device
= 2 X 0.040 amps
= 1 X.0.040 amps
= 1 X.0.200 amps
FACP
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
ANN-BUS Devices
= 0.080 amps
= 0.040 amps
= 0.200 amps
= 0.320 amps