Swift™ Wireless Slc Devices; Maximum Number Of Devices; Wiring Requirements For Sd Devices; 1: Wire Sizing On 5815Xl For Sd Devices - Honeywell Farenhyt Series Installation And Operation Manual

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

Model Number
SD505-PHOTO
SD505-HEAT
SD505-6AB
SD505-6IB
SD505-6RB
SD505-6SB
SD505-DUCT
SD505-DUCTR
SD500-PS/-PSDA
SD500-AIM
SD500-MIM
SD500-ANM
SD500-ARM
SD500-SDM
SD500-LIM
SD505-DTS-K
7.4 SWIFT™ Wireless SLC Devices
The WIDP-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the IFP-300/ECS. It is
powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply. Available wireless devices include a photo detec-
tor, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise detector, and a monitor module. For updated details about
wireless devices, system setup and operation see the SWIFT
or LS10036-001SK-E for more information.

7.5 Maximum Number of Devices

The IFP-300/ECS supports IDP, SK, SD, or SWIFT™ wireless SLC devices. The maximum number of SLC devices per panel is 300 for
IDP or SK devices, or 254 if using SD devices. The number of SLC expanders is limited only by the SBUS bandwidth, point count, and
1A SBUS current limit. Device support is as follows:
• IDP or SK Devices - The IFP-300/ECS supports a total of 300 IDP or SK points. The SLC points can be all sensors or all
modules or any combination of modules and sensors.
or
• SD Devices - The IFP-300/ECS system can support a total of 254 SD SLC detectors and modules, in any combination. SD
devices are only supported on the 5815XL.
or
• SWIFT Wireless Devices–A SWIFT Gateway system supports up to 50 devices: 1 SWIFT Gateway and up to 49 (in any
combination) wireless detectors and monitor modules. Multiple Gateways can be used.

7.6 Wiring Requirements for SD Devices

The following information applies to SLC devices. Refer to the section that describes the type of device you are installing for details.
7.6.1 Wire Sizing on 5815XL for SD Devices
The wire can be untwisted, unshielded, solid or stranded as long as it meets the National Electric Code 760-51 requirements for power
limited fire protective signaling cables. Wire distances are computed using copper wire.
Maximum wiring resistance is 50 ohms for SD devices.
79
Model Name/Description
Photoelectric smoke detector.
Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
6" base
6" short circuit isolator base
6" relay base
6" sounder base
Duct Smoke Detector. Duct Housing including the SD505- Analog Photoelectric
Smoke Sensor. Intake tubing for duct available in three lengths: SD505-T2 (2.5 foot);
SD505-T5 (5 foot); SD505-T10 (10 foot)
Duct Detector housing with relay base. Duct housing with relay base including SD505-
Analog Photoelectric Smoke detector preinstalled
Single or dual action addressable pull station
Addressable input module (switch input), standard size, DIP switch configurable
Mini input monitor module (switch input), small size, DIP switch configurable.
Addressable notification module
Addressable relay module DIP switch configurable.
Addressable smoke detector module.
Line isolator module. Fits in a double gang box.
Remote test switch & LED indicator for the SD505-DUCTR
Table 7.3 SD SLC Devices
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
®
Smart Wireless Integrated Fire Technology Manual # LS10036-001FH-E
Installation
Instructions
PN
150955
I56-3541-00
I56-3542-00
I56-3540-00
1700-09882
1700-09882
I56-3632-00
I56-3547-00
I56-3544-00
I56-3545-00
I56-3546-00
I56-3543-00
1700-09882