Engineering via SICAM WEB
Example: single-point information output
·
In the directory tree, mark the corresponding DO module
·
Click on the side bar left beside the status area, if you want to extend it
·
Mark the row with the desired datapoint
Control area:
·
Select a "New value"
·
Click on the button
The new process value is transferred to the target device and displayed in the column Value.
Type Identifications and Possible Values
The following type identifications and attributes are supported to force a new process value:
Type identification
Single-point information
(TI 30)
Single command (TI 45)
Double command (TI 46)
Tap position command
(TI 47)
Measured value normal-
ized (TI 34)
Measured value scaled
(TI 35)
Measured value short
floating point (TI 36)
Setpoint command nor-
malized (TI 48)
Setpoint command scaled
(TI 49)
Setpoint command short
floating point (TI 50)
232
New value
Select
before
execute
Off (0)
On (1)
Off (0)
On (1)
Off (01)
No
On (10)
Yes
Lower (01)
Higher (10)
-1...+1
-32768...
+32767
15
-1.000•10
...
15
+1.000•10
-1...+1
-32768...
No
+32767
Yes
15
-1.000•10
...
15
+1.000•10
Qualifier of command
No determination
Long command execution time
Short command execution time
Persistent command
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
Origi-
nator
0...255