Use Cases
F.3
SICAM CMIC as Telecontrol Substation with Integrated
Switch for External System Connection
Features:
·
Communication with the control system via IEC 60870-104
(Ethernet-Interface, X1 or X4, can be set with parameter)
·
Communication with the external system via IEC 60870-104
(Ethernet-Interface, X1 or X4, can be set with parameter)
·
SICAM CMIC is used as switch between control system and external system
·
1 IP address
·
1 subnet mask
·
1 default router
·
Parameter
address (connected ports in switch mode)
Office Zone
Control Center Zone
Substation Zone
398
Network settings | IP adress | Mode of Ethernet Ports
SICAM CMIC
Control Center
IP-address:
Subnet mask: 255.255.0.0
Router
IP-address:
172.16.0.254
PREx / ET84
IP-address: 172.16.0.3
X1
Subnet mask: 255.255.0.0
Default router: 172.16.0.254
X4
IP-address:
172.16.0.4
External
Subnet mask: 255.255.0.0
device
Default router: 172.16.0.254
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016
=
1 IP
172.17.0.22