Siemens SICAM CMIC User Manual page 200

Remote terminal units
Table of Contents

Advertisement

Engineering via SICAM WEB
Processing type
200
Parameter
Command_prolong_t
RS_outp_same_state_1
Sync_Input_t
1_out_of_n_t
RS_Mon_Source
Sw_Seq_command_seq
Sw_Seq_addtl_com
SID-BSE
SID-ST
SID-SSE
QOC>8
RS_Image
Meaning
Command prolongation time in seconds (S)
0.01 to 327.67
Selection of command output and command
confirmation, if return state is already end po-
sition before output.
Attention: only active if RS_mon_t is ≠ 0.
Within this time (in sec) the enabling over the
syncronisation input must occur on the com-
mand.
0 = no syncronisation over syncronisation in-
put.
Attention: Function only active if sync_t = 0
0.1 to 6553.5
Within this time (in sec) the 1 out of n enabling
must occur on the command.
0 = no 1 out of n enabling necessary.
Attention: Function only active if sync_t = 0.
0.1 to 25.5
Source of state information for state infor-
mation monitoring
· Peripherals
· open-/closed loop control function
· both (logical OR)
Switching sequence: output additional com-
mand before or after the command
Switching sequence: Select the additional
command
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254. If
automatic then the source ID will be learned.
Source identification supplementary system
element
If QOC > 8 (Qualifier of Command) is accept-
ed, so all QOC > 8 will be interpreted as
QOC = 0
Parameter works only with ACP 1703 platform
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016