Engineering via SICAM WEB
Category
Process value digital
Protocol element control
message
178
Parameter
pva_X_100%
pva_Y_0%
pva_Y_100%
pva_Decimal_places
pva_Unit_text
pvd_Event
pvd_Alarm
pvd_Process_Text
pvd_State_TextOn
pvd_State_TextOff
pvd_State_TextFlt
pvd_State_TextInt
pvd_Process_GroupNbr
pvd_Process_GroupPos
QID-BSE
QID-ST
QID-SSE
Control_function_(PRE)
Edge_(PRE)
PRE_(CM)
Meaning
Value adaptation: Upper limit of the used
measuring range in the external (protocol
specific) format. The corresponding internal
value is defined at Y_100%.
Value adaptation: Lower limit of the used
measuring range in the selected internal for-
mat. The internal format is defined at TI (type
identification). The corresponding external
value is defined at X_0%.
Value adaptation: Upper limit of the used
measuring range in the selected internal for-
mat. The internal format is defined at TI (type
identification). The corresponding external
value is defined at X_100%.
Count of decimal places (max. 7)
The value is displayed with this unit text
(max. 8 characters)
The data point is displayed in the event list
The data point is displayed in the alarme list
The data point is displayed with this name
(max. 13 characters)
The state ON for single or double point infor-
mation is displayed with this name (max.
6 characters)
The state OFF for single or double point in-
formation is displayed with this name (max.
6 characters)
The state faulty position for double point in-
formation is displayed with this name (max.
6 characters)
The state intermediate position for double
point information is displayed with this name
(max. 6 characters)
The data point is displayed in the cockpit in
this group (1...32)
The data point is displayed in the cockpit on
this position (1...255)
Source identification basic system element
Source identification station number if mul-
tipoint traffic mode 0...99 if R-SID 0...254. If
automatic then the source ID will be learned.
Source identification supplementary system
element
· 0...239 = function defined by protocol ele-
ment
· 240 = GI request
· 241 = reserved
· 242 = control location
· 244 = CASDU selective GI request
· 245...255 = reserve for further BSE func-
tions
· Positive edge
· Negative edge
· State (0 = function, 1 = function + 1)
Protocol element number
· PRE0...PRE3
· distribute over multimaster function
SICAM RTUs, User Manual SICAM CMIC
DC8-001-2.09, Edition 08.2016

Advertisement

Table of Contents
loading